Hitachi UTOPIA RAS-4HVRP2E Service Manual page 135

Hide thumbs Also See for UTOPIA RAS-4HVRP2E:
Table of Contents

Advertisement

6 Optional functions
RAS-(4-6)H(V)(R/N)(C/P)2E
No.
Setting Item
19
Hot gas bypass control disabled
Thermo-OFF setting for outdoor unit
20
after defrosting operation
Intermitent operation of outdoor fan
21
motor
22
Not prepared
23
Not prepared
24
Not prepared
25
Not prepared
26
Not prepared
27
High static pressure mode setting
Crankcase heater control during
28
stoppage
29
Not prepared
30
Not prepared
31
Not prepared
Permit indoor fan operation during
32
forced stoppage
33
Not Prepared
34
Not Prepared
133
SMGB0136 rev.0 - 07/2021
7-Segment
Display
Initial setting
Hot gas bypass control disabled
Initial setting
Forced stop upon return from defrosting
Initial setting
Intermittent fan operation (30[s] run / 570[s] stop)
Intermittent fan operation (60[s] run / 540[s] stop)
Intermittent fan operation (120[s] run / 480[s] stop)
Intermittent fan operation (300[s] run / 300[s] stop)
-
-
-
-
-
No setting
Static pressure setting
No setting
Enable the control to restrain heater standby power
-
-
-
No setting
Change of forced stop state
-
-
Contents