Hitachi UTOPIA RAS-4HVRP2E Service Manual page 207

Hide thumbs Also See for UTOPIA RAS-4HVRP2E:
Table of Contents

Advertisement

9 Servicing
RAS-(4-6)H(V)(R/N)(C/P)2E

Disassembly / Assembly the control PCB (PCB1)
1 Disassembly the service cover according to the item "9.3.1 Removing service cover".
2 Disconnect all the wiring connected to the control PCB.
3 Remove the 6 fixing holders -2- and disassembly the control PCB -1-.
4 Assembly the new control PCB -1- and fix it with 6 holders -2-.
5 Connect all the wiring connected to the control PCB as it was originally.
6 Assembly the service cover according to the item "9.3.1 Removing service cover".

Disassembly / Assembly the Inverter module (PCB2)
1 Disassembly the upper cover according to the item
2 Open the electrical box according to the item "Opening / Closing Electrical box (P plate)".
3 Disconnect all the wiring connected to the Inverter module.
-
DCL1 (Reactor)
-
DCL2 (Reactor)
-
CN331 (NF)
-
CN16 Aerial connector (compressor)
-
PCN2 (pressure switch control)
-
CN206 (PCB communication)
-
R, S, T (NF)
4 Remove the 8 fixing screws -2- and disassembly the control PCB -1-.
-
Recommended the use of a flexible screwdriver or if necessary, remove the PCB3 according to the item
"Disassembly / Assembly the PCB3"
5 Pull the Inverter and remove along with the plastic case and the radiation fin.
6 Assembly the new control PCB -1- and fix it with 8 screws -2-.
205
SMGB0136 rev.0 - 07/2021
1
2
"9.3.3 Removing upper cover".
to improve the access to the right side screws.
9