Temperature Control - VendNet ST 3000 Service Manual

Single temp/variable temp glass front vendor
Table of Contents

Advertisement

0.0.6 LIFT OPTICS ALIGN
This indicates if the Delivery Lift Sensors are functioning and aligned so that they can detect when a product is lifted to the
correct height. The Green LED on the lift optics board (located behind the iVend Red LED sensor board) will also be illuminated
when sensors are aligned.

TEMPERATURE CONTROL

To prevent damage to the refrigeration unit when it is turned off or the power is interrupted, the refrigeration unit will not restart for at
least three minutes regardless of the temperature.
SENSORS
Temperature sensor(s) are positioned to best represent the product temperature. The sensor(s) are monitored by the control system.
The refrigeration and optional heater systems are activated depending on the target temperature setting or SET POINT. The total
allowable temperature variation from the SET POINT is DELTA.
SENSOR1
Single Zone versions have SENSOR1 located near the top-right of the vendor cabinet assembly. Dual Zone versions have SENSOR1
located under the dual zone barrier on the right side of the cabinet assembly.
SENSOR2
Dual Zone versions may have an optional SENSOR2 mounted near the top-right of the vendor cabinet assembly.
S T / V T V E N D O R • 3 5 6 8 3 5 6 7 3 5 6 6 3 5 6 5 •
STEP
1
Press the 'Service Mode'
board.
2
Press
3
Press
Press
Shows current state of sensors. OK is
unblocked and ready . NO is blocked or not
4
operational. The time counter allows for determining
how long a product or object is blocking the sensors.
5
Press
3 times to exit
button on the control
19
DISPLAY
(Motor count)
Diagnostics
Peripherals
Lift Optics Align
OK or NO
0000 ms
Back to sales mode
4 2 2 0 5 5 7 R e v A