Connecting and commissioning

8.1

Overview of safety and commissioning

Dangerous electrical voltage
When electrical devices are used, certain parts of them have to carry dangerous voltages.
Failure to observe the operating instructions can therefore lead to serious injuries or
material damage.
Observe the operating instructions.
Risk of injury during commissioning
• The door movements cannot always be externally controlled while the controller is being
• During the learn run, the force is > 75 N and the energy > 4 J.
• An authorized person must therefore be posted near the door to ensure that no one else
Note
Learn run
The motor temperature must not be below 0 °C during the learn run, as otherwise the mass
to be moved will be incorrectly determined, and the opening and closing speed may lie in an
impermissible range.
Note
Measures for complying with temperature class T3
The following measures are required for the operation of the controller to comply with
temperature class T3:
• Use the 24 V output voltage only for operating the control inputs (max. 100 mA)
• Use a sufficiently large (at least 350 x 350 mm), unpainted, metal mounting plate
• The maximum drive parameters are restricted to the default values
• The maximum air temperature of 85 °C must not be exceeded in the vicinity of the printed
circuit board
SIDOOR ATD400T door control units for railway applications
System Manual, 06/2020, A5E42201947-AB
WARNING
WARNING
commissioned (in particular during the automatic determination of parameters). The
light barrier is not active during the learn run.
can enter the vicinity of the door during commissioning.
8
89