Return From Storage - Generac Power Systems RD015 Owner's Manual

Stationary diesel generators
Hide thumbs Also See for RD015:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Troubleshooting
Remove right side access panel. See Subsection 5.2 —Access Panels.
10.
Remove oil drain hose from holding clamp.
11.
Use one wrench to hold hex on hose fitting (to prevent rotation), and use second wrench to remove drain plug.
12.
Drain oil into a suitable container.
13.
Install drain plug onto end of oil drain hose.
14.
Install oil drain hose into holding clamp.
15.
Rotate oil filter counterclockwise to remove from oil filter adapter.
16.
Apply a light coat of clean engine oil to gasket of new oil filter.
17.
Install oil filter by hand until gasket just contacts oil filter adapter. Tighten oil filter an additional 3/4 to one full turn.
18.
Remove oil fill cap and fill engine with the recommended oil. See Subsection 2.3 —Engine Oil Recommenda-
19.
tions.
Install oil fill cap.
20.
Install right side access panel. See Subsection 5.2 —Access Panels.
21.
NOTE: Dispose of used oil and oil filter at a proper collection center.
Remove left side access panel. See Subsection 5.2 —Access Panels.
22.
NOTE: On 2.3L models, remove ten screws to release louvered air intake panel.
$
Always disconnect the negative battery cable first. If the positive cable should contact ground with the
negative cable installed, the resulting sparks may cause a battery explosion which could result in seri-
ous injury.
Remove battery negative cable (black) from battery negative (-) terminal.
23.
Remove battery positive cable (red) from battery positive (+) terminal.
24.
Remove two screws to release battery hold-down clamp from platform.
25.
Remove battery and store on a wooden board in a cool, dry room. Do not store the battery on a concrete or
26.
earthen floor.
Install left side access panel. See Subsection 5.2 —Access Panels.
27.
NOTE: On 2.3L models, start ten screws to install louvered air intake panel. Alternately tighten screws to 90 in-
lbs.
Thoroughly clean and wipe down the generator. See Subsection 2.7 —Corrosion Protection.
28.
6.4.2— Return From Storage
To return the unit to service after storage, proceed as follows:
Thoroughly clean and wipe down the generator. See Subsection 2.7 —Corrosion Protection.
1.
Remove left side access panel. See Subsection 5.2 —Access Panels.
2.
NOTE: On 2.3L models, remove ten screws to release louvered air intake panel.
Install battery onto tray oriented with the negative (-) post toward the front of the enclosure.
3.
Install two screws with nylon washers to secure battery hold-down clamp to tray.
4.
Check battery. See Subsection 5.7.7—Check Battery Condition/Fluid Level..
5.
$
Always connect the positive battery cable first. If the positive cable should contact ground with the
negative cable installed, the resulting sparks may cause a battery explosion which could result in seri-
ous injury.
Install battery positive cable (red) onto battery positive (+) terminal.
6.
Install battery negative cable (black) onto battery negative (-) terminal.
7.
48
Owner's Manual for Stationary Diesel Generators

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rd020Rd030Rd048Rd0500066781

Table of Contents