FlameSpec IR3 H2 HD User Manual
Doc. No. F140V0020.07
FlameSpec IR3-H2-HD
4222 E. La Palma Ave, Anaheim, CA 92807 USA T: (+1) 714-671-8500
www.fg-detection.com · support@fg-detection.com

Advertisement

Table of Contents
loading

Summary of Contents for FGD FlameSpec IR3 H2 HD

  • Page 1 FlameSpec IR3 H2 HD User Manual Doc. No. F140V0020.07 FlameSpec IR3-H2-HD 4222 E. La Palma Ave, Anaheim, CA 92807 USA T: (+1) 714-671-8500 www.fg-detection.com · support@fg-detection.com...
  • Page 2 Information FlameSpec-IR3-H2-HD Triple IR HD Flame Detector User Guide, October 2022 Copyright © Fire & Gas Detection Technologies Inc. All rights reserved. The owner or authorized user of a valid copy of this manual may reproduce this publication for the purpose of learning to use the specified equipment.
  • Page 3: Table Of Contents

    FlameSpec IR3 H2 HD User Manual Doc. No. F140V0020.07 Table of Contents 1. Introduction ........................1 Key Features ........................1 Model Number Description ....................2 Internal tests ........................2 Product Overview ........................3 Accessories ..........................4 Installation ........................7 General Considerations ......................7 Preparations for Installation ....................10 Required Tools ........................
  • Page 4 FlameSpec IR3 H2 HD User Manual Doc. No. F140V0020.07 Window Heater ......................... 23 Video Settings ........................23 Modbus Address ........................ 23 Manual BIT – Alarm Output Test (Full loop test) ..............24 Operation ........................25 Output Signals ........................25 Testing..........................26 Flame Simulator .........................
  • Page 5 FlameSpec IR3 H2 HD User Manual Doc. No. F140V0020.07 List of Figures Figure 1 - Front view of the FLS-IR3-H2-HD....................... 3 Figure 2 - Rear view of the FLS-IR3-H2-HD ....................... 3 Figure 3 - Tilt mount ................................4 Figure 4 - Weather Cover ..............................4 Figure 5 - Pole Mount ...............................
  • Page 6: Introduction

    FlameSpec IR3 H2 HD User Manual F140V0020.07 1. Introduction The FlameSpec-IR3-H2-HD flame detector will detect hydrogen and other “energy transition” fires quickly allowing actions to be initiated to minimize the extend of the fire. The detector addresses slow growing fires as well as fast eruptions of fire using improved IR3 technology.
  • Page 7: Model Number Description

    FlameSpec IR3 H2 HD User Manual F140V0020.07 Model Number Description Model No are defined as follows FLS-IR3-H2-HD - A S X X Standard Near IR Camera Like model 1 with RGB Camera Designed for, but not limited to, automotive spray paint applications where compliance with 0.5 s response (per NFPA 33) is needed.
  • Page 8: Product Overview

    FlameSpec IR3 H2 HD User Manual F140V0020.07 Product Overview 1 - F FLS-IR3-H2-HD IGURE RONT VIEW OF THE 2 - R FLS-IR3-H2-HD IGURE EAR VIEW OF THE For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com...
  • Page 9: Accessories

    FlameSpec IR3 H2 HD User Manual F140V0020.07 Accessories 1.5.1 Mounting Bracket The detector should be mounted using the stainless-steel tilt mount part number FLS-TMO- S02. This allows the detector to be securely attached to a wall, pole or other solid surface using appropriate fixings.
  • Page 10: Figure 5 - Pole Mount

    FlameSpec IR3 H2 HD User Manual F140V0020.07 1.5.3 Pole mount The pole mount enables the detectors to be installed with its tilt mount brackets. The pole mount kit we supply are suitable for 2-inch or 3- inch poles. Part number FLS-PMA-S23.
  • Page 11: Figure 7 - Flame Simulator Kit

    FlameSpec IR3 H2 HD User Manual F140V0020.07 1.5.5 Flame Simulator The FLS-IR3-H2-HD may be tested using the FLS- FSIM-IR3-H2-KIT. The FlameSpec flame simulator family provides a fast and convenient means of periodically testing the detector and control system end-to-end. Maintenance costs can be reduced as the detectors can be tested in situ without needing a hot work permit.
  • Page 12: Installation

    FlameSpec IR3 H2 HD User Manual F140V0020.07 Installation This chapter does not attempt to cover all standard practices and codes of installation. Rather, it emphasizes specific points of consideration and provides some general rules for qualified personnel. You must always observe special safety precautions.
  • Page 13: Figure 9 - Horizontal Field Of View

    FlameSpec IR3 H2 HD User Manual F140V0020.07 9 - H IGURE ORIZONTAL IELD OF 10 - V IGURE ERTICAL IELD OF For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com...
  • Page 14 FlameSpec IR3 H2 HD User Manual F140V0020.07 Environment • Environmental conditions including but not limited to dust, snow or rain can reduce the detectors sensitivity and require additional consideration. Hot Work • Arc welding should not be performed within 12 ft. (3.5m) of the detector. It is recommended that the system be inhibited during welding operations in situations where the possibility of a false alarm cannot be tolerated.
  • Page 15: Preparations For Installation

    FlameSpec IR3 H2 HD User Manual F140V0020.07 Preparations for Installation The installation must comply with national and local regulations and standards applicable to flame detectors (e.g., NFPA 72) and all local and common engineering practices. It is recommended to consult with the authority having jurisdiction.
  • Page 16 FlameSpec IR3 H2 HD User Manual F140V0020.07 • If the equipment is likely to come into contact with corrosive and/or other harsh substances, consult with the relevant technical persons to take suitable precautions to prevent the detector from being adversely affected, thus ensuring that the type of protection is not compromised.
  • Page 17: Mounting The Tilt Mount

    FlameSpec IR3 H2 HD User Manual F140V0020.07 Mounting the Tilt Mount The tilt mount enables the detector to be rotated up to 45 degrees (horizontal/vertical) in all directions. The following installation instructions show how to use it to support the detector from below (the preferred method).
  • Page 18: Mounting The Detector

    FlameSpec IR3 H2 HD User Manual F140V0020.07 Mounting the detector Use the following steps to connect the detector to the tilt mount, referring to Figure 13 : a) Place the detector, with its cable/conduit entries pointing down, on the holding plate of the tilt mount (item 2).
  • Page 19: Electrical Wiring

    FlameSpec IR3 H2 HD User Manual F140V0020.07 Electrical Wiring Warning • The sensor module in the front half of the detector contains no serviceable components and should never be opened. Opening will invalidate the warranty of the detector. The terminal compartment at the back is the only part of the housing that should be opened by the user.
  • Page 20: Table 1: Terminal Connections

    “24 VDC (-)” terminals (2 or 12)”. See 3.11 Manual BIT – Alarm Output Test for more details. RS 485 (+) RS-485 Modbus communication (used by the “FGD Communicator” software) RS 485 (-)
  • Page 21: Current Output (0-20Ma) Wiring

    FlameSpec IR3 H2 HD User Manual F140V0020.07 Current Output (0-20mA) Wiring The detector’s 0-20mA current output can act as both a source or a sink transmitter and can be 3-wire or 4-wire connected. The following drawing shows how to wire the detector to act as a current source isolated...
  • Page 22: Figure 17 - Source 3-Wire Scheme

    FlameSpec IR3 H2 HD User Manual F140V0020.07 The following drawing shows how to wire the detector to act as a current source non-isolated transmitter (3-wire connection): 24VDC Return Controller Detector 17 – S IGURE OURCE CHEME Note: Link between 3 and 11 to be wired on site...
  • Page 23: Wire Relay Connection

    FlameSpec IR3 H2 HD User Manual F140V0020.07 4 Wire Relay Connection This wiring option uses the fault and alarm relay and are connected to fire alarm panels. This connection allows to connect several detectors on 4 wires in a single loop. On the last detector there is a connected EOL resistor in the connection box.
  • Page 24: Cabling Recommendations

    FlameSpec IR3 H2 HD User Manual F140V0020.07 each repeater) up to 247 on the same 4 wires. Using the RS-485 network, it is possible to read each detector’s status (fault, alarm) and to initiate a BIT to each detector individually.
  • Page 25: Earth/Ground Regime

    Some functions of the detector can be configured using an RS-485 modem connected to a computer with the “FGD communicator” software. For details of how to download the software please contact technical support on: (+1) 714-671-8500 or via email at support@fg-detection.com These configuration options are listed in the following table along with their factory default values.
  • Page 26: Table 2: Detector Configuration Options

    FlameSpec IR3 H2 HD User Manual F140V0020.07 2: D ABLE ETECTOR ONFIGURATION PTIONS Function Options Default Setting Sensitivity Very low, Low, Medium, High, Extreme Medium Ultra-fast detection Disabled, Enabled Disabled Alarm Delay 0, 5, 10, 20 or 30 seconds 0 seconds (no delay)
  • Page 27: Sensitivity

    FlameSpec IR3 H2 HD User Manual F140V0020.07 Sensitivity The detector can be configured to one of five sensitivity levels: very low, low, medium, high and extreme. The following table lists for each sensitivity setting the maximum distance, in which a...
  • Page 28: Enable Pre-Alarm 0-20Ma

    NTSC or PAL format, depending on the “Video analog output” setting Modbus Address The detector can communicate with the FGD communicator software using a Modbus RTU compatible protocol on RS-485. This protocol allows for a network of detectors to be connected, each with a unique Modbus address.
  • Page 29: Manual Bit - Alarm Output Test (Full Loop Test)

    FlameSpec IR3 H2 HD User Manual F140V0020.07 Manual BIT – Alarm Output Test (Full loop test) When enabled, the alarm outputs are activated when a Manual BIT is initiated. See section 4.2 for details. WARNING Make sure all fire extinguishing actions or alarms connected to the detector are DISABLED when the manual BIT is initiated and the “Manual BIT –...
  • Page 30: Operation

    FlameSpec IR3 H2 HD User Manual F140V0020.07 4 Operation The FlameSpec-IR3-H2-HD is a triple-IR flame detector that includes a built-in high-definition video camera module. The video module automatically records video of alarm events and can provide live video of the detection zone to a screen in the control room.
  • Page 31: Testing

    The BIT process runs automatically at startup and periodically during the operation of the detector. The BIT can also be initiated manually by connecting the “Manual BIT” terminal and the “24 VDC (-) “terminal for one second (see Table 1) or by using the FGD communicator software (connected through RS-485).
  • Page 32: Maintenance

    FlameSpec IR3 H2 HD User Manual F140V0020.07 5 Maintenance After powering up, the detector should work maintenance free. Regular checks should be in the form of a physical inspection and to periodically ensure the optical surfaces are clean (windows and reflective mirror). It is also recommended to perform a function test annually or in line with local requirements, whichever is the sooner.
  • Page 33: Troubleshooting

    FlameSpec IR3 H2 HD User Manual F140V0020.07 6 Troubleshooting Use the table below to help troubleshoot any detector operational issues. Detector Status Possible Cause Corrective Action LEDs Off No power to the unit Check that the power is connected to the •...
  • Page 34: Servicing

    Refer to the detector warranty statement in section 12. 8 FGD Communicator Software The FGD Communicator software can be used to configure and monitor the FlameSpec-IR3 flame detector. The software communicates using Modbus over an RS-485 port to the detector. Modbus commands enable the user to configure parameters and monitor the status of the detector.
  • Page 35: Specifications

    FlameSpec IR3 H2 HD User Manual F140V0020.07 9 Specifications Fire Detection • Detection time and distance: o 40ms - for fast fire burst or explosion o 1.5s - for 32″ (0.8m) hydrogen fire at 0–66ft. (0–20m) o 4s - for 32″ (0.8m) hydrogen fire at 66–100ft. (20–30m) o Field of view: 90°...
  • Page 36: Outputs

    FlameSpec IR3 H2 HD User Manual F140V0020.07 Outputs o Relays: Volt-free contacts rated 2A at 30 VDC o Alarm: Normally open o Auxiliary: Normally open o Fault : Closed when energized o 0-20mA (stepped) current output: 3 wire and 4 wire configurations (sink and source). HART® 7.
  • Page 37: Product Labeling

    FlameSpec IR3 H2 HD User Manual F140V0020.07 Product Labeling 9.7.1 Ex db For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com...
  • Page 38 FlameSpec IR3 H2 HD User Manual F140V0020.07 9.7.2 Ex db eb For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com...
  • Page 39 FlameSpec IR3 H2 HD User Manual F140V0020.07 9.7.3 Warning Label For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com...
  • Page 40: Approvals

    FlameSpec IR3 H2 HD User Manual F140V0020.07 Approvals Note: All items are designed and tested to meet the relevant requirements. o Explosion proof: o ATEX: II 2 G D Ex db IIC T5 Gb or Ex db eb IIC T5 Gb and Ex tb IIIC T95°C Db -55°C<Ta<75°C Ex db IIC T4 Gb or Ex db eb IIC T4 Gb and Ex tb IIIC T105°C Db -55°C<Ta<85°C...
  • Page 41: Performance

    FlameSpec IR3 H2 HD User Manual F140V0020.07 10 Performance The following tables show test results of detection distances and times for different fire scenarios. Each table lists results for a different sensitivity setting. For liquid fires the size of fire refers to the size of the pan, filled with the fuel.
  • Page 42: False Alarm Immunity

    FlameSpec IR3 H2 HD User Manual F140V0020.07 False Alarm Immunity The following table shows test results of false alarm immunity for detectors configured to “Extreme” sensitivity. For each radiation source a distance is listed. This is the minimum tested distance, from which the detectors did not alarm when exposed to the radiation source (either modulated or non-modulated).
  • Page 43: Ordering Information

    FlameSpec IR3 H2 HD User Manual F140V0020.07 11 Ordering Information Part Number Description Flame Detector FLS-IR3-H2-HD-AS11 FlameSpec IR3-H2-HD, ATEX, FMus, FMc and IECEx certified, 316SS, M25 Entries with Near IR camera FLS-IR3-H2-HD-AS21 FlameSpec IR3-H2-HD, ATEX, FMus, FMc and IECEx certified, 316SS, 3/4”NPT Entries with Near IR camera...
  • Page 44: Warranty

    FlameSpec IR3 H2 HD User Manual F140V0020.07 12 Warranty FIRE & GAS DETECTION TECHNOLOGIES INC. agrees to extend to Purchaser/Distributor a warranty on the FIRE & GAS DETECTION TECHNOLOGIES INC. supplied components of the FlameSpec products. FIRE & GAS DETECTION TECHNOLOGIES INC. warrants to Purchaser/Distributor that the products are free from defects in materials and workmanship for a period of five (5) years, commencing with the date of delivery to Purchaser/Distributor.
  • Page 45 FlameSpec IR3 H2 HD User Manual F140V0020.07 Appendix A HART 7 Communications Highway Addressable Remote Transducer (HART®) establishes digital data communication over 4-20mA Current Loop cables. The HART protocol uses FSK modulation signals superimpose at low level on top of the 4-20mA current.