FGD FlameSpec UV-IR User Manual

FGD FlameSpec UV-IR User Manual

Flame detector
Hide thumbs Also See for FlameSpec UV-IR:

Advertisement

Quick Links

www.acornfiresecurity.com
FlameSpec UV-IR User Manual
F110V0020.05
FlameSpec UV-IR
FlameSpec UV-IR-F
www.acornfiresecurity.com

Advertisement

Table of Contents
loading

Summary of Contents for FGD FlameSpec UV-IR

  • Page 1 FlameSpec UV-IR User Manual F110V0020.05 FlameSpec UV-IR FlameSpec UV-IR-F www.acornfiresecurity.com...
  • Page 2 www.acornfiresecurity.com FlameSpec-UV-IR UV/IR Flame Detector User Guide, May 2020 Copyright © Fire & Gas Detection Technologies Inc. All rights reserved. The owner or authorized user of a valid copy of this manual may reproduce this publication for the purpose of learning to use the specified equipment.
  • Page 3: Table Of Contents

    FlameSpec UV-IR User Manual Doc. No. F110V0020.05 Table of Contents 1. Introduction .........................1 Key Features..........................1 Model Number Description ...................... 2 Internal tests ..........................2 Installation...........................3 General Considerations ......................3 Preparations for Installation ....................5 Required Tools ......................... 5 Certification Instructions ......................
  • Page 4 FlameSpec UV-IR User Manual Doc. No. F110V0020.05 Troubleshooting ........................18 Specifications ........................19 Fire Detection ......................... 19 Electrical Specifications ......................19 Outputs ..........................19 Mechanical Specifications ...................... 20 Environmental Specifications ....................20 Label Figures .......................... 21 Approvals ..........................22 Electromagnetic Compatibility ....................22 Warranty ...........................23...
  • Page 5 FlameSpec UV-IR User Manual Doc. No. F110V0020.05 List of Figures Figure 1: Tilt Mount Base - Rear View ......................7 Figure 2: Tilt mount base – Side View ......................8 Figure 3: Detector on Tilt Mount – Side View ....................9 Figure 4 –...
  • Page 6: Introduction

    FlameSpec UV-IR User Manual F110V0020.05 1. Introduction The FlameSpec-UV-IR flame detector provides ultra-fast response, high performance and reliable detection of a large variety of fires including hydrocarbon fires (visible and non-visible), as well as hydrogen fires (FLS- UV-IR only).
  • Page 7: Model Number Description

    FlameSpec UV-IR User Manual F110V0020.05 1.2 Model Number Description Model No are defined as follows: FLS-UV-IR-F - X S X 1 FLS-UV-IR - X S X 1 1 - M25 2 - ¾” NPT A – FM, ATEX 1.3 Internal tests During normal operation, the flame detector performs self-tests of its optics, electronics and software.
  • Page 8: Installation

    FlameSpec UV-IR User Manual F110V0020.05 2 Installation The detector is intended for use as part of a complex system where many detectors and other devices are integrated with different vendors’ systems and interface communication to a variety of different types and configuration control units and panels including control of instrumentations computers.
  • Page 9 FlameSpec UV-IR User Manual F110V0020.05 Environment ▪ Environmental conditions including but not limited to dust, snow or rain can reduce the detectors sensitivity and require additional maintenance. Welding ▪ Arc welding should not be performed within 10 ft. (3m) of the detector. It is recommended that the system be inhibited during welding operations in situations where the possibility of a false alarm cannot be tolerated.
  • Page 10: Preparations For Installation

    FlameSpec UV-IR User Manual F110V0020.05 2.2 Preparations for Installation The installation must comply with local regulations and standards applicable to flame detectors (e.g., NFPA 72) and all local and common engineering practices. It is recommended to consult with a safety engineer.
  • Page 11 FlameSpec UV-IR User Manual F110V0020.05 • Installation shall be carried out in accordance with the applicable code of practice by suitably trained personnel. • Inspection and maintenance of this equipment shall be carried out by suitably trained personnel in accordance with the applicable code of practice.
  • Page 12: Installing The Tilt Mount

    FlameSpec UV-IR User Manual F110V0020.05 2.5 Installing the Tilt Mount The tilt mount enables the detector to be rotated up to 45 degrees (horizontal/vertical) in all directions. The following installation instructions show how to use it to support the detector from below (the preferred method).
  • Page 13: Installing The Detector

    FlameSpec UV-IR User Manual F110V0020.05 The following drawing is a side view of the tilt mount: Figure 2: Tilt mount base – Side View 2.6 Installing the detector Use the following steps to connect the detector to the tilt mount, referring to Figure 3:...
  • Page 14: Figure 3: Detector On Tilt Mount - Side View

    FlameSpec UV-IR User Manual F110V0020.05 3, 4 Figure 3: Detector on Tilt Mount – Side View ITEM ITEM NAME TILT MOUNT ASSEMBLY HOLDING PLATE MOUNTING HEX SCREWS M8 AND LOCK WASHERS HEX SOCKET LOCKING SCREW M8 HEX SOCKET LOCKING SCREW M12...
  • Page 15: Configuration Options

    FlameSpec UV-IR User Manual F110V0020.05 3 Configuration options Some functions of the detector can be configured using an RS-485 modem connected to a computer with the “FDG communicator” software. These configuration options are listed in the following table along with their factory default values.
  • Page 16: Ultra-Fast Detection

    3.6 Modbus Address The detector can communicate with the “FGD communicator” software using a Modbus RTU compatible protocol on RS-485. This protocol allows for a network of detectors to be connected, each with a unique Modbus address. The address of the detector can be set to any value in the range 1–247.
  • Page 17: Detector Wiring

    See 3.7 Manual BIT – Alarm Output Test for more details. Shield This terminal should be left connected to the housing internal ground screw. RS 485 (+) RS-485 Modbus communication (used by the “FGD Communicator” software) RS485 (-) Fault Relay (NC) Alarm Relay (NC)
  • Page 18: Current Output (0-20Ma) Wiring

    FlameSpec UV-IR User Manual F110V0020.05 4.2 Current Output (0-20mA) Wiring The detector’s 0-20mA current output can act as both a source or a sink transmitter and can be 3- wire or 4-wire connected. The following drawing shows how to wire the detector to act as a current source isolated transmitter...
  • Page 19: Figure 6 - Source 3-Wire Scheme

    FlameSpec UV-IR User Manual F110V0020.05 The following drawing shows how to wire the detector to act as a current source non-isolated transmitter (3-wire connection): 24VDC Return Controller Detector 6 – S IGURE OURCE CHEME The following drawing shows how to wire the detector to act as a current sink non-isolated...
  • Page 20: Rs-485 Communication Network

    (fault, alarm) and to initiate a BIT to each detector individually. The detector communicates via RS-485 with a Modbus RTU compatible protocol. For more details on the communication protocol, please consult with FGD. Figure 8: RS-485 Networking www.acornfiresecurity.com...
  • Page 21: Operation

    FlameSpec UV-IR User Manual F110V0020.05 5 Operation The FlameSpec-UV-IR is a UV/IR flame detector ready for detecting fire approximately 30 seconds after power up. During this startup time the LED flashes Yellow. If the startup is successful, the indication LED turns to green, the 0-20mA indicates 4mA and the fault relay is closed.
  • Page 22: Testing

    The BIT process runs automatically at startup and periodically during the operation of the detector. The BIT can also be initiated manually by short circuiting the “Manual BIT” terminal and the “24 VDC (-)“ terminal for one second (see Table 3) or by using the FGD communicator software (connected through RS-485).
  • Page 23: Troubleshooting

    FlameSpec UV-IR User Manual F110V0020.05 c) Where dust, dirt or moisture accumulates on the window, first clean the window with a soft optical cloth and detergent, and then rinse with a clean soft cloth, cotton swab, or tissue. 5.4 Troubleshooting...
  • Page 24: Specifications

    FlameSpec UV-IR User Manual F110V0020.05 6 Specifications 6.1 Fire Detection • Detection time and distance: o FLS-UV-IR: ▪ 5ms - for fast fire burst or explosion ▪ 1s - for 1ft (0.1m ) N-heptane pan fire at 0-50 ft (0-15m) ▪...
  • Page 25: Mechanical Specifications

    FlameSpec UV-IR User Manual F110V0020.05 • 0-20mA (stepped) current output: 3 wire and 4 (isolated) wire configurations (sink and source). The 0-20 mA output at different detectors status are define at the below table. The max load of 0-20 is max 500 ohm at 18-32 VDC. The 0-20 mA is sink isolated and can be configured as source.
  • Page 26: Label Figures

    FlameSpec UV-IR User Manual F110V0020.05 6.6 Label Figures 6.6.1 Ex db 6.6.2 Ex db eb www.acornfiresecurity.com...
  • Page 27: Approvals

    FlameSpec UV-IR User Manual F110V0020.05 6.7 Approvals Note: All items are designed and tested to meet the relevant requirements. • Explosion proof: o ATEX: II 2 G D Ex db IIC T5 Gb or Ex db eb IIC T5 Gb and Ex tb IIIC T95°C Db -55°C<Ta<75°C Ex db IIC T4 Gb or Ex db eb IIC T4 Gb and Ex tb IIIC T105°C Db -55°C<Ta<85°C...
  • Page 28: Warranty

    FlameSpec UV-IR User Manual F110V0020.05 7 Warranty FIRE & GAS DETECTION TECHNOLOGIES INC. agrees to extend to Purchaser/Distributor a warranty on the FIRE & GAS DETECTION TECHNOLOGIES INC. supplied components of the FlameSpec products. FIRE & GAS DETECTION TECHNOLOGIES INC. warrants to Purchaser/Distributor that the products are free from defects in materials and workmanship for a period of five (5) years, commencing with the date of delivery to Purchaser/Distributor.
  • Page 29: Appendix A Response Characteristics Fls-Uv-Ir

    FlameSpec UV-IR User Manual F110V0020.05 Appendix A Response Characteristics FLS-UV-IR Response to different fire scenarios The following tables show test results of detection distances and times for different fire scenarios. Each table lists results for a different sensitivity setting. For liquid fires the size of fire refers to the size of the pan, filled with the fuel.
  • Page 30 FlameSpec UV-IR User Manual F110V0020.05 Medium Sensitivity Fuel Size Distance Feet Average Response Time (Seconds) N-Heptane 1 x 1 ft 49 (15) Gasoline 1 x 1 ft 49 (15) Methane 32-in Plume 30 (9) 32-in Plume 33 (10) Diesel...
  • Page 31: False Alarm Immunity

    FlameSpec UV-IR User Manual F110V0020.05 False Alarm Immunity The following table shows test results of false alarm immunity for detectors configured to “Extreme” sensitivity. For each radiation source a distance is listed. This is the minimum tested distance, from which the detectors did not alarm when exposed to the radiation source (either modulated or non-modulated).
  • Page 32: Appendix B Response Characteristics Fls-Uv-Ir-F

    FlameSpec UV-IR User Manual F110V0020.05 Appendix B Response Characteristics FLS-UV-IR-F Response to different fire scenarios The following tables show test results of detection distances and times for different fire scenarios. Each table lists results for a different sensitivity setting. For liquid fires the size of fire refers to the size of the pan, filled with the fuel.
  • Page 33: False Alarm Immunity

    FlameSpec UV-IR User Manual F110V0020.05 1 x 1 ft 36 (11) Kerosene 1 x 1 ft 36 (11) Methanol 1 x 1 ft 30 (9) Ethanol 1 x 1 ft 31 (9.5) Isopropanol 1 x 1 ft 36 (11)
  • Page 34 FlameSpec UV-IR User Manual F110V0020.05 www.acornfiresecurity.com...