Table 2: Detector Configuration Options - FGD FlameSpec IR3 H2 HD User Manual

Table of Contents

Advertisement

FlameSpec IR3 H2 HD User Manual
Function
Sensitivity
Ultra-fast detection
Alarm Delay
Alarm Latch
Video module
Video analog output
Enable Pre-Alarm 0-20mA
Enable dirty window warning 0-
20mA
Aux. Relay
Window Heater
Modbus address
Manual BIT – Alarm Output Test
Note: Medium, sensitivity setting allows detection of a 32-in Plume hydrogen flame at a
distance of 66ft (20m).
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com
T
2: D
C
ABLE
ETECTOR
ONFIGURATION
Very low, Low, Medium, High, Extreme
Disabled, Enabled
0, 5, 10, 20 or 30 seconds
Disabled, Enabled
Disabled, Enabled
Disabled, NTSC, PAL
Disabled, Enabled
Disabled, Enabled
Alarm
Pre-Alarm
Dirty Window Warning
Disabled, Enabled
1 – 247
Disabled, Enabled
F140V0020.07
O
PTIONS
Options
Default Setting
Medium
Disabled
0 seconds (no delay)
Disabled
Enabled
Disabled
Disabled
Disabled
Alarm
Enabled
1
Disabled
21

Advertisement