Touchscreen devices

You can connect the TruVu™ ET Display to the TV-OPT's Ethernet Service port to view or change the controller's
driver properties. You can also create a custom Touch file to provide a graphic representation of the controlled
equipment or to provide access to schedules, view trends and alarms, and more without having to access the
system's server.
NOTES
These touchscreen devices are not powered by the Ethernet port.
The TruVu™ ET Display requires a 24 Vdc external power source.
CAUTION A touchscreen device can share a power supply with the Carrier controller if:
The power source shared by the controller and Equipment Touch is AC power.
The power source shared by the controller and TruVu™ ET Display is DC power.
You maintain the same polarity.
You use the power source only for Carrier controllers.

Chiller system configurations

The program is scalable, so it can be applied from a minimal system including only the chiller and chilled water
pump components, to a larger system, including condenser water side components and air handling unit fans, as
illustrated below.
Even though the controller works with a variety of chilled water system components, it must be used with parallel
chiller systems and operates best with variable speed pumps and variable speed fans.
TV-OPT
Installation and Start-up Guide
5
What is the TV-OPT?
©2022 Carrier.