Rotary Switch Settings - Carrier TV-OPT Installation And Startup Manual

Table of Contents

Advertisement

Addressing the TV-OPT

Rotary switch settings

Rotary switch settings (see example below) are used to determine the following items in your system, so you
should plan carefully before setting the switches.
If you use a Default IP address, the final octet is the number created by the three rotary switch settings (must
be a unique number from 1 to 253). See To set the IP address (page 14).
If you autogenerate the following:
Device Instance, the number is automatically set to a number equal to the ((IP network number x 100) +
rotary switch settings).
BACnet Network Number for Port S1, the number is automatically set to a number equal to the ((IP network
number + rotary switch settings) x 10).
Autogenerating is set up through the controller setup pages (page 35).
The rotary switch settings determine the router number in the i-Vu® interface.
EXAMPLE The switches below are set to 125.
CAUTION Do not leave the rotary switches set at 0 (the factory default). The TV-OPT cannot be discovered if
the rotary switches are left at 0.