Addressing the TV-OPT
Rotary switch settings
Rotary switch settings (see example below) are used to determine the following items in your system, so you
should plan carefully before setting the switches.
•
If you use a Default IP address, the final octet is the number created by the three rotary switch settings (must
be a unique number from 1 to 253). See To set the IP address (page 14).
•
If you autogenerate the following:
Device Instance, the number is automatically set to a number equal to the ((IP network number x 100) +
rotary switch settings).
BACnet Network Number for Port S1, the number is automatically set to a number equal to the ((IP network
number + rotary switch settings) x 10).
Autogenerating is set up through the controller setup pages (page 35).
•
The rotary switch settings determine the router number in the i-Vu® interface.
EXAMPLE The switches below are set to 125.
CAUTION Do not leave the rotary switches set at 0 (the factory default). The TV-OPT cannot be discovered if
the rotary switches are left at 0.
TV-OPT
Installation and Start-up Guide
12
©2022 Carrier.
All rights reserved.