Modbus Settings; Modbus Interface Configuration - Kampmann 148941 User Manual

Climate controller
Table of Contents

Advertisement

1.96
Climate Controller Type 148941 / Type 148942 / Type 148943 / Type 148944
Operation manual

10 Modbus Settings

10.1 Modbus Interface Configuration

10.2 Modbus - Parameter List
Datenpunktbeschreibung
Intern temperature sensor
Extern temperature sensor
Operating condition controller
Control variable controller
Alert notification
Filter alert
State input 1
State input 3
Heating Setpoint
Cooling Setpoint
Offset Setpoint
Default setpoint Offset
Default operating condition On/Off
Eco / Day
Default Change - Over
To configure the Modbus interface, please open Modbus
settings
by
pressing
approximately 3 seconds.
The modbus master interface and the climate control
interface (as a slave) have to be adjusted equally.
The default settings of the modbus interface are:
Transmission Code:
Adresse:
Baud Rate:
Parity:
Stop Bits:
Wertebereich
0 – 500 ≙ 0 – 50°C
0 – 500 ≙ 0 – 50°C
0: Off
1: Heating
2: Cooling
0 – 100 ≙ 0 – 100%
11: Control sensor damaged
12: Engine error
13: Room frost protection
14: Condensation alarm
15: General error
16: Extern sensor damaged
17: Unit frost protection
0: inactive
1: active
0: open
1: closed
0 – 500 ≙ 0 – 50°C
0 – 500 ≙ 0 – 50°C
0 – 500 ≙ 0 – 50°C
-90 – 90 ≙ -9,0 – 9,0°C
0: On
1: Off
0: Eco
1: Day
0: Heating
1: Cooling
65535: no Function
5
and
6
simultaneously
RTU, Slave Mode
32
19200
Gerade
2
Registertyp
Protokoll Adresse
Input Register
Input Register
Input Register
Input Register
Input Register
Input Register
Input Register
Input Register
Input Register
Input Register
Input Register
Holding Register
Holding Register
Holding Register
Holding Register
for
514
515
525
524
528
529
519
520
511
512
513
257
262
264
261
29