Electrical Wiring; Cabling - Kampmann 148941 User Manual

Climate controller
Table of Contents

Advertisement

1.96
Climate Controller Type 148941 / Type 148942 / Type 148943 / Type 148944
Operation manual

9.3 Electrical Wiring

9.4 Cabling

Term.
connection Type
1
EC fan
2
EC fan
3
4
Output 2
5
Output 1
6
Input 3
7
L
8
N
9
Input 1
10
11
Input 2
12
Important
*): Shielded cable, IY(ST)Y 0.8 mm or similar. Lay separately
from high-voltage cables.
**): Shielded paired cable e.g UNITRONIC® BUS LD 2x2x0.22
or similar. Lay separately from high-voltage cables.
All other connections can be done with NYM-J (or similar).
Wire cross-sections of unshielded cables are not specified, as
the length of the cable is involved in the calculation of the cross-
section.
Specifies the number of wires including protective conductor.
GND
0...10 V, max. 5 mA
230 V AC, max. 3A
230 V AC, max. 3A
Digital/230 V AC
Universal/potential-free
Digital/potential-free (type: 148941 & 148942)
Modbus interface (type: 148943 & 148944)
Route all low voltage cables along
the shortest route.
Ensure that low voltage and power
cables are separated, using metal
partitions on cable harnesses.
Use only shielded cables as low
voltage cables
25

Advertisement

Table of Contents
loading

This manual is also suitable for:

148942148943148944

Table of Contents