Parameter Settings; Setpoint - Kampmann 148941 User Manual

Climate controller
Table of Contents

Advertisement

1.96
Climate Controller Type 148941 / Type 148942 / Type 148943 / Type 148944
Operation manual

8 Parameter Settings

8.1 Setpoint

In this menu, you can adjust setpoints and limit values, as well as room
temperature control functions.
Base setpoint:
Minimum
Maximum
Adjustment range:
Increment:
Frost protection (room frost protection)
Heat protection
Unit frost protection
Presence/Offset
Special system requirements can be configured using parameter
settings in the Expert menu. The following system requirements are
available:
Display
Lock operating functions
Type of setpoint setting
Inputs and outputs
Sensor calibration
Control and regulation parameters
The expert level is protected by the password "0022".
Base setpoint for room temperature control. Both with relative value
and absolute value temperature setting.
Lower limit of the adjustment range of the absolute setpoint.
Upper limit of the adjustment range of the absolute setpoint.
Maximum offset of the control setpoint to the base setpoint with
relative value temperature setting.
Increment width for temperature adjustment.
Temperature at which the room frost protection function and the
corresponding alarm is enabled.
Temperature at which the heat protection function is enabled.
Temperature at which the unit frost protection function and the
corresponding alarm is enabled.
Hold:
Offset is retained when changing from occupied to
unoccupied.
Offset is set to "0" when changing from occupied to
Reset:
unoccupied.
This function is valid for the relative and absolute value
temperature setting.
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

148942148943148944

Table of Contents