☐ You must be logged in as Installer.
Procedure:
1. Go to Control Functions > Genset control function > Minimum genset load via the page and menu
selection.
2. Set the desired parameters (see Section 4.8.3, page 19).
8.2

Configuring Reverse Power Protection of the Gensets

Figure 26: Settings for reverse power protection of the gensets
User Manual
Description
Ramp time of the change in the
nominal genset active power in
seconds
Setpoint offset related to the mini-
mum genset loading threshold in
%
Value
Explanation
1 s to 60 s
−100 % ... 100 %
8 System Control
Default
value
10 s
5 %