Page 1
OPC UA I/O User Manual V4.0, 2021/09 U-7500 Series IIoT OPC UA I/O Module U-7555M U-7560M U-7504M U-7526M Technical support: service@icpdas.com Technical Editor: Tim Chen Editor: Eva Li...
Page 2
OPC UA I/O Series User Manual V4.0 – ICP DAS Warranty All products manufactured by ICP DAS are under warranty regarding defective materials for a period of one year, beginning from the date of delivery to the original purchaser. Warning ICP DAS assumes no liability for any damage resulting from the use of this product.
OPC UA I/O Series User Manual V4.0 – ICP DAS Revision History This chapter provides revision history information to this document. The table below shows the revision history. Revision Date Description Version: Provide New Functions 1. Add CH3.3 Rule Setting (Main new function: Logic) * CH4.5 Advanced Setting: add 4.5.3 Rule Setting * Setting the logic condition of I/O &...
Page 4
OPC UA I/O Series User Manual V4.0 – ICP DAS Revision Date Description version: 1. Release new AIO models: UA-7504M/UA-7526M V2.0 09/2020 2. Provide new function: Scaling Initial issue 1. Release new DIO models: UA-7555M/UA-7560M V1.0 06/2020 2. Provide OPC UA and MQTT communication functions...
OPC UA I/O Series User Manual V4.0 – ICP DAS Content of Table Revision History ........................ 3 Content of Table ........................ 5 1. UA I/O Introduction: ...................... 8 1.1 Introduction ......................8 1.2 Features ........................ 9 1.3 Selection Guide ....................10 1.4 Specifications.......................
Page 6
OPC UA I/O Series User Manual V4.0 – ICP DAS 3.2.2 MQTT Client Setting of the UA I/O ................ 40 3.2.3 Secure Encrypted Connection: MQTT Certificate ..........45 3.3 Rule Setting ......................46 Setting Steps: ..................46 3.4 RESTful API: Read and Write I/O and Virtual Point ..........50 What is Restful API? ................
Page 7
OPC UA I/O Series User Manual V4.0 – ICP DAS Digital Input ..................73 Digital Output ..................73 Analog Input ..................74 Analog Output ..................74 4.2.3 Project File......................75 Download the file from device .............. 75 Upload the file to the device ..............76 4.3 Main Menu - OPC UA Setting ................
OPC UA I/O Series User Manual V4.0 – ICP DAS 1. UA I/O Introduction: UA I/O series is a series of OPC UA I/O modules, also known as U-7500. The main model is U-75xxM. This series built-in provides the communication protocol functions of the Industrial Internet of Things (IIoT), including OPC UA Server and MQTT Client functions.
OPC UA I/O Series User Manual V4.0 – ICP DAS 1.2 Features Built-in OPC UA Server Service Compliance with IEC 62541 Standard. Provides functions of Active Transmission, Transmission Security Encryption (SSL/TLS), User Authentication (X.509 Certificates / Account password), Communication Error Detection and Recovery, etc. to connect SCADA or OPC UA Clients. Recommend to keep the maximum number of sessions within 3 connections.
OPC UA I/O Series User Manual V4.0 – ICP DAS 1.3 Selection Guide U-7500 Series UA I/O Selection Guide: U-7500 Series OPC UA I/O Module Selection Guide Module Type Type Type Type Dry (Source), Open Collector U-7555M (Sink) (Sink,Source) Power Relay...
OPC UA I/O Series User Manual V4.0 – ICP DAS 1.4 Specifications 1.4.1 Software Specifications (Series Common) UA I/O Software Specifications (Series Common) Protocol ● OPC Unified Architecture: 1.02 ● Core Server Facet ● Data Access Server Facet ● Method Server Facet ●...
Page 12
OPC UA I/O Series User Manual V4.0 – ICP DAS UA I/O Software Specifications (Series Common) RESTful API ● User can read/write the I/O & Virtual points through HTTP. Rule Setting ● Provide simple logic condition rule setting, let UA I/O do automatic condition judgment and action control, to achieve simple AI.
OPC UA I/O Series User Manual V4.0 – ICP DAS 2. Quick Start: Hardware/Network Connection This chapter describes the UA I/O module’s hardware connection, network connection and quick setting. For how to set up a project via the Web UI on the browser, please refer to Chapter 3. 2.1.
Page 23
OPC UA I/O Series User Manual V4.0 – ICP DAS Jumper Location: U-7504M Channel Vin3 Vin2 Vin1 Vin0 Vout3 Vout2 Vout1 Vout0 Jumper U-7526M Channel Vout1 Vout0 Vin5 Vin4 Vin3 Vin2 Vin1 Vin0 Jumper Jumper Direction (Jumpers default as: Input: Voltage Output: Voltage.
OPC UA I/O Series User Manual V4.0 – ICP DAS 2.1.3. Hardware Wiring Connect the U-7500 I/O Module with the RJ-45 Ethernet port to an Ethernet switch/hub and PC (Fig.1). Beside, U-7500 support PoE (Power over Ethernet). If using the PoE switch, do not need one more power supply (Fig.2 for PoE Switch).
OPC UA I/O Series User Manual V4.0 – ICP DAS 2.2. Network Connection This section introduces 3 methods to connect to the UA I/O Web UI (User Interface). Setting new UA I/O module or the new user please uses the method A in the Chapter 2.2.1...
OPC UA I/O Series User Manual V4.0 – ICP DAS 2.2.1. Connection by Factory Default Settings (For New UA) The factory default settings of the UA I/O series are as the following table: Factory Default Settings of UA I/O Modules 192.168.255.1 Assign U-7500 a new IP setting Network...
Page 27
OPC UA I/O Series User Manual V4.0 – ICP DAS 3. Click 【System Setting】【Account Setting】, change the Username/password first, or user cannot use any other function (New design for data security). Password Setting rules:...
Page 28
OPC UA I/O Series User Manual V4.0 – ICP DAS 4. Click【System Setting】【Network Setting】【Network Setting(LAN1)】to change the IP setting by user network. 5. Save the IP setting, restore the PC original IP settings, and type the new IP in the browser as step-2 to login the Web UI of UA I/O.
OPC UA I/O Series User Manual V4.0 – ICP DAS 2.2.2. Connection by Utility Searching Setting new UA I/O or the new user please uses the method in the Chapter 2.2.1. (Method A) If the UA I/O has a fixed IP and in the same domain as the PC, users can directly enter the IP in the address bar of a web browser and log in to the Web UI of the UA.
Page 30
OPC UA I/O Series User Manual V4.0 – ICP DAS Create a new connection Click “New” to add a connection item and give a name for it. Search the UA controller Mouse double-click on the name you created (or single-click and then click the “Connect” button), this utility will scan and list all UA devices over the network.
Page 31
OPC UA I/O Series User Manual V4.0 – ICP DAS Connect to the UA Device Click the device name you want to connect to, and then click the “Connect” button. It will connect to the UA webpage via the default Web browser (IE/Chrome…). Connection to the UA Web UI The default web browser will be run and direct go to the UA login web site.
Page 32
OPC UA I/O Series User Manual V4.0 – ICP DAS Login the Web UI of the UA I/O Series When login into the web interface, the UA default home page (the main configuration screen) will as below, and will automatically read setting of that UA to the webpage.
OPC UA I/O Series User Manual V4.0 – ICP DAS 3. Main Function Settings This chapter introduces some of the most important and commonly used functions of UA I/O and their setting steps. OPC UA I/O modules is a series of Ethernet I/O modules that built-in with the OPC UA Server and MQTT Client services.
OPC UA I/O Series User Manual V4.0 – ICP DAS 3.1 Settings for Using OPC UA Connection This section introduces how to set up the OPC UA communication service of UA I/O, and recommends compatible ICP DAS products. UA I/O module built-in OPC UA Server Service that compliance with IEC 62541 Standard. Provides functions of Active Transmission, Transmission Security Encryption (SSL/TLS), User Authentication (X.509 Certificates / Account password), Communication Error Detection and Recovery, etc.
OPC UA I/O Series User Manual V4.0 – ICP DAS 3.1.1 OPC UA Server Connection Settings (UA I/O) UA I/O module built-in OPC UA Server function and itself is the Server side of the connection. So, when setting up the Server, you only need to set the connection port number and choose the login method (via anonymous, username, or certificate).
OPC UA I/O Series User Manual V4.0 – ICP DAS 3.1.2 OPC UA Client Side: InduSoft Simple Application After setting the OPC UA Server-side (UA I/O), you only need to configure the OPC UA Client for connection. Now, go to the Client device that connects with UA I/O, and set the corresponding data point.
OPC UA I/O Series User Manual V4.0 – ICP DAS 3.1.3 Secure Encrypted Connection: OPC UA Certificate When using the OPC UA connection, in addition to the account login for security, users can also enable the certificate login to double the protection by the secure encryption. This section describes how to download/upload the certificates.
OPC UA I/O Series User Manual V4.0 – ICP DAS 3.2 Settings for Using MQTT Connection This section introduces how to set up the MQTT Client communication of UA I/O, and recommends the compatible ICP DAS products. UA I/O module built-in MQTT Client Service (Compliance with MQTT V.3.1.1 protocol).
OPC UA I/O Series User Manual V4.0 – ICP DAS 3.2.1 Connecting to MQTT Broker UA I/O module built-in MQTT Client function and itself is the Client side of the connection. So, when setting up the MQTT Broker, it is to set the data of the remote device (Broker) that the UA I/O module wants to connect.
OPC UA I/O Series User Manual V4.0 – ICP DAS 3.2.2 MQTT Client Setting of the UA I/O UA I/O built-in MQTT Client function and itself is the MQTT Client side of the connect. When setting, please set the connecting remote MQTT Broker device first, and then set the UA I/O module of the MQTT client.
Page 41
OPC UA I/O Series User Manual V4.0 – ICP DAS MQTT Client Setting of the UA I/O: Manu Path:【MQTT Setting】【Client Setting】 (Appendix 1. Set an update frequency for the task data. Default: 1000 (Unit: ms) 2. Give a dead bend value for updating a float signal. 3.
Page 42
OPC UA I/O Series User Manual V4.0 – ICP DAS The setting parameters for Both enable or disable the JSON Format: MQTT Setting > Client Setting - Publish & Subscribe Publish Topic The topic of sending data / publishing message. Publish QoS The publish Qos (Quality of Service) levels.
Page 43
OPC UA I/O Series User Manual V4.0 – ICP DAS Group Setting example: Check “Enable” of “JSON Format” Here is an example of the lighting control in a factory. Use the I/O points of the U-7555M module to connect the light switches of Room 1 to 7 in the factory Building-A to monitor/control the on/off of the room lights.
Page 44
OPC UA I/O Series User Manual V4.0 – ICP DAS Singly Setting example: Uncheck “Enable” of “JSON Format” Here is an example of the lighting control in a factory. Use the I/O points of the U-7555M module to connect the light switches of Room 1 to 7 in the factory Building-A to monitor/control the on/off of the room lights.
OPC UA I/O Series User Manual V4.0 – ICP DAS 3.2.3 Secure Encrypted Connection: MQTT Certificate When using the MQTT connection, in addition to the account login for security, users can also enable the SSL/TLS login to use the MQTT Certificate protection of the secure encryption. This section describes how to download/upload the certificates.
OPC UA I/O Series User Manual V4.0 – ICP DAS 3.3 Rule Setting 本節說明 UA I/O 的邏輯控制功能 “規則設定” 如何設定,提供簡易的邏輯判斷規則腳本,讓 UA I/O 做自動判斷和控制,達到簡易的智能化。 Manu Path: 【Advanced Setting】【Scaling】 (Appendix Setting Steps: First, click [ Advanced Setting] > [ Rule Setting], switch to the rule setting screen, to add the condition. Select an I/O point, to add a condition rule.
Page 47
OPC UA I/O Series User Manual V4.0 – ICP DAS Select an I/O point, to add a condition rule.
Page 48
OPC UA I/O Series User Manual V4.0 – ICP DAS Click the “Delete” icon indicated by the green arrow to delete the rule condition. Set up the “IF, THEN, ELSE” conditions/actions to add the rule according to the above steps. Then, click the "...
Page 49
OPC UA I/O Series User Manual V4.0 – ICP DAS Red box part: AND or OR means that all judgment conditions are AND or OR. Example: Condition 1 Condition 2 Condition 3... Example: Condition 1 Condition 2 Condition 3... Changing the sampling interval time to speed up the rule judgment. Click “Save” to write the settings of this page to the device.
OPC UA I/O Series User Manual V4.0 – ICP DAS 3.4 RESTful API: Read and Write I/O and Virtual Point This section describes RESTful API functions and usage. UA I/O supports RESTful API functions. Users can remotely read and write the I/O points (include the virtual point) of UA I/O modules through HTTP. ...
Page 51
OPC UA I/O Series User Manual V4.0 – ICP DAS [ Example 2. ] IP/VariableInformation?VirtualTag0 : RESTful Read the value of VirtualTag0 Or as following: IP/VariableInformation?U-7504M_DI.DI0 : RESTful Read the DI.DI0 value of U-7504M. [ Example 3. ] IP/VariableInformation : RESTful write the value of VirtualTag0 This example uses the Firefox as the RESTful client.
OPC UA I/O Series User Manual V4.0 – ICP DAS RESTful Description [Resource Definition] Remarks HTTP Method Path Description Link to Example Read all variable data. /AllVariableName G1.1 Read the data of var0, var1, var2… /VariableInformation?var0 Link to Example in all variables, data are separated ,var1, var2…...
Page 53
OPC UA I/O Series User Manual V4.0 – ICP DAS [GET Examples] Resource Definition Actual Application Corresponding to the Resource Definition GET /AllVariableName GET /AllVariableName Description Back to G1.1 GET:Read /AllVariableName:All variables For Example: GET /AllVariableName:Read all variable data, and the return value is in JSON format. Resource Definition Actual Application Corresponding to the Resource Definition GET /VariableInformation?var0, var1,...
Page 54
OPC UA I/O Series User Manual V4.0 – ICP DAS [PUT Example] Resource Definition Actual Application Corresponding to the Resource Definition PUT /VariableInformation PUT /var/use [RAW Body] "Var1": { "Quality": "Good", "Value": "24.5" "Var2": { "Quality": "Good", "Value": "24.5" Description Back to P1.1 PUT:Write /VariableInformation:Variable Information.
OPC UA I/O Series User Manual V4.0 – ICP DAS 4. Main Menu: Parameter Descriptions This chapter introduces the menu functions of the UA I/O web UI and more focused on the function parameters of the menu. Each section introduces one main menu and its sub-menu functions. The function location is showing in a brief text and diagram of【Menu Path】, for Menu Path introductions please refer to Appendix A.
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.1.2 Network Setting Function: Display and set up the network settings of the UA I/O. Support Module: All UA I/O modules support this function. Manu Path:【System Setting】【Network Setting】 (Appendix ...
OPC UA I/O Series User Manual V4.0 – ICP DAS Hostname Setting System Setting > Network Setting - Hostname Setting Hostname The host name of this UA I/O. Default: system value. User can give a new name, but cannot be null, Chinese characters, or special symbols. Save Click to save the settings of this item.
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.1.3 Time Setting Function: Display and set up the date and time of the UA I/O. Support Module: All UA I/O modules support this function. Manu Path:【System Setting】【Time Setting】 (Appendix ...
OPC UA I/O Series User Manual V4.0 – ICP DAS NTP time calibration System Setting > Time Setting - NTP time calibration Functional Status NTP Server: Click to display the setting columns for NTP Server. Custom Time Server: Click to display the setting columns for Custom Time Server. NTP Server Select the common time server provided by the system.
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.1.4 Account Setting Function: Display and set up the login username and password of the UA I/O Web UI. Support Module: All UA I/O modules support this function. Manu Path:【System Setting】【Account Setting】 (Appendix System Setting >...
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.1.5 Web Server Setting Function: Provide Web Server settings, such as display and set the Web Server port. Support Module: All UA I/O modules support this function. Manu Path: 【 System Setting】 【Web Server Setting】 ...
OPC UA I/O Series User Manual V4.0 – ICP DAS Https Web Server Setting System Setting > Https Web Server Setting Port Https Web Server port of the UA I/O device. Factory default port: 8888. Certificate The server certificate required for HTTPS communication. File name rule: [A-Z, a-z, 0-9].crt, only .crt files composed of English uppercase and lowercase and numbers are accepted.
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.1.6 Firewall Setting Function: Provide firewall settings, allowing specific IP to have permission to connect to the module. Support Module: All UA I/O modules support this function. Manu Path:【System Setting】【Firewall Setting】 (Appendix System Setting >...
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.1.7 Firmware Setting Function: Provide firmware settings, such as restore factory setting and update firmware. Support Module: All UA I/O modules support this function. Manu Path:【System Setting】【Firmware Setting】 (Appendix ...
Page 65
OPC UA I/O Series User Manual V4.0 – ICP DAS 3. After the process finished, it appears a box message "During device restart, after waiting for 60 seconds, press OK", indicating that this restoration succeeds. If the box does not pop up, this restoration fails.
OPC UA I/O Series User Manual V4.0 – ICP DAS Update Firmware When UA I/O has new functions, users can go to the UA series download center on the ICP DAS website to download the latest version of Firmware software, and then update the firmware of your UA I/O module according to the steps in this section.
Page 67
OPC UA I/O Series User Manual V4.0 – ICP DAS 4. After upload the file, it begins to install the firmware. 5. After the process finished, it appears a box message "During device restart, after waiting for 60 seconds, press OK", indicating that this update succeeds.
OPC UA I/O Series User Manual V4.0 – ICP DAS Maintenance This function is only provided to ICP DAS R&D personnel for maintenance using. It is reserved and not open for use.
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.2 Main Menu - Module Setting This main menu aggregates all module and project in the module related function settings. This chapter focuses on parameter descriptions. About the detailed steps and notices for using OPC UA connection/certificate, please refer to 3.1 Settings for Using OPC UA Connection Chapter 3 Main...
OPC UA I/O Series User Manual V4.0 – ICP DAS Digital Output Module Setting > I/O Setting - Digital Output Channel The channel name (number) of the UA I/O hardware. MQTT Alias The variable alias of the sending message (MQTT JSON format), when using MQTT connection.
OPC UA I/O Series User Manual V4.0 – ICP DAS Analog Input Module Setting > I/O Setting – Analog Input Channel The channel name (number) of the UA I/O hardware. MQTT Alias The variable alias of the sending message (MQTT JSON format), when using MQTT connection.
OPC UA I/O Series User Manual V4.0 – ICP DAS Analog Output Module Setting > I/O Setting – Analog Output Channel The channel name (number) of the UA I/O hardware. MQTT Alias The variable alias of the sending message (MQTT JSON format), when using MQTT connection.
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.2.2 I/O Status Function: Display and change the I/O status of the UA I/O module. Support Module: All UA I/O modules support this function. Manu Path:【Module Setting】【I/O Status】 (Appendix ...
OPC UA I/O Series User Manual V4.0 – ICP DAS Analog Input Module Setting > I/O Status – Analog Input Channel The channel name (number) of the UA I/O hardware. Value Current channel status value. When the input type is 4-20mA, if an abnormal state occurs, the value will display as -32.768.
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.2.3 Project File Function: download and upload the project file of the UA I/O module. Support Module: All UA I/O modules support this function. Manu Path:【Module Setting】【Project File】 (Appendix ...
OPC UA I/O Series User Manual V4.0 – ICP DAS Upload the file to the device Upload the project file into the UA I/O. This function can quickly replace the previously backed up project file, and then restore the project setting parameters. Click [Upload] button, select the project file in the PC.
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.3 Main Menu - OPC UA Setting This main menu aggregates all OPC UA related settings. This chapter focuses on parameter descriptions. About the detailed steps and notices for using OPC UA connection/certificate, please refer to Settings for Using OPC UA Connection Chapter 3 Main Function Settings.
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.3.1 Server Setting Function: Provide the Server settings for using OPC UA connection. Support Module: All UA I/O modules support this function. Manu Path:【OPC UA Setting】【Server Setting】 (Appendix OPC UA Setting > Server Setting - Connection Setting Port The communication port number of the OPC UA Server.
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.3.2 Certificate Function: When selecting OPC UA certificate connection, the UA I/O (Server side) needs to exchange the certificate with the connecting client side. This page is about setting the OPC UA Certificate for the security and encryption, e.g.
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.4 Main Menu – MQTT Setting This main menu aggregates all MQTT related settings. This chapter focuses on parameter descriptions. About the detailed steps and notices for using MQTT connection/certificate, please refer to 3.2 Settings for Using MQTT Connection Chapter 3 Main Function...
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.4.2 Client Setting Function: Provide the MQTT Client settings for using MQTT connection. Support Module: All UA I/O modules support this function. Manu Path:【MQTT Setting】【Client Setting】 (Appendix MQTT Setting > Client Setting – Content Setting Scan Rate(ms) Set an update frequency for the task data.
Page 82
OPC UA I/O Series User Manual V4.0 – ICP DAS JSON Format: Enable (message is sent as a group): MQTT Setting > Client Setting - Publish & Subscribe (JSON Format: Enable) Publish Topic The topic of sending data / publishing message. Publish QoS The publish Qos (Quality of Service) levels.
Page 83
OPC UA I/O Series User Manual V4.0 – ICP DAS JSON Format: Not Enable (message is sent in singly): MQTT Setting > Client Setting - Publish & Subscribe (JSON Format: Enable) Details Check “Unfold” to display all fields. Channel The I/O channel name of the hardware.
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.4.3 Certificate Function: When selecting MQTT certificate connection, the UA I/O needs to exchange the certificate with the connecting device. This page is about setting the MQTT Certificate for the security and encryption.
Page 85
OPC UA I/O Series User Manual V4.0 – ICP DAS Parameter Function Descriptions: One-way Authentication Screen Two-way Authentication Screen MQTT Setting > Certificate – Upload the file to the device Authentication One-way authentication: The Client verifies the validity of Broker credentials;...
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.5 Main Menu – Advanced Setting This main menu aggregates the advanced settings, such as the Scaling setting that function can convert the analog signal to a more readable value. The scaling function is only available for AI/AO channels. ICP DAS will develop more advanced functions in the future.
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.5.2 Event Log Function: When the I/O value changes, record the current I/O value for easy device tracking in the future. Support Module: All UA AI/AO modules support this function. ...
Page 88
OPC UA I/O Series User Manual V4.0 – ICP DAS Advanced Setting > Event Log –Analog Input / Output Alias The alias name in function of [Module Setting] > [I/O Setting] Deadband Set the Deadband value for updating floating-point data. Default: 1 Deadband: Dead zone, inactive zone.
OPC UA I/O Series User Manual V4.0 – ICP DAS 4.5.3 Rule Setting Function: The Rule Setting function provides simple logic condition rule setting, let UA I/O do automatic condition judgment and action control, to achieve simple AI. Support Module: All UA AI/AO modules support this function. ...
OPC UA I/O Series User Manual V4.0 – ICP DAS 5. Recovering Firmware Setting (Reset) This chapter explains how to use the Reset button to recover the firmware settings. The steps are as follows: 1. Please find the Reset button on the UA I/O bottom side, and then press the Reset button. 2.
Page 91
OPC UA I/O Series User Manual V4.0 – ICP DAS 5. After restarting, the module will recover the UA I/O settings as follows: Recovering Firmware of UA I/O Modules IP (LAN) Keep the original setting Assign UA I/O a new IP setting Network Netmask Keep the original setting...
OPC UA I/O Series User Manual V4.0 – ICP DAS Appendix A. Menu Path Diagram Description 【Menu Path】diagram shows the main menu function section path in a brief way that user can follow the menu path order (text/diagram) to select the main menu and the sub-menu, then can go to the function setting web page.
OPC UA I/O Series User Manual V4.0 – ICP DAS Appendix B. MQTT JSON Format of the UA I/O Series MQTT JSON Example & Format Descriptions: Name Descriptions "Variable" : [ { Variable The array name of JSON. "Name" : "Bool_R[0]", Its structure includes several "Attribute"...