ELECTRICAL AND CONTROL SETTINGS
Mark
Part name
5
DHW tank's thermistor
6
Common thermistor
Thermistor for water outlet temperature
7
of second cycle
Thermistor for water outlet temperature
8
after hydraulic separator
9
Common thermistor
Thermistor for swimming pool water
10
temperature
Thermistor for second ambient
11
temperature
11
4-20 mA application
12
13
Common line
14
Input 1 (Demand ON/OFF) (*)
15
Input 2 (ECO mode) (*)
16
Common line
17
Input 3 (Swimming pool) (*)
18
Input 4 (Solar) (*)
19
Input 5 (Smart function) (*)
20
Input 6 (DHW boost) (*)
21
Input 7 (Power meter)
22
Aquastat security for circuit 1 (WP1)
23
24(C)
Mixing valve close
25(O)
Mixing valve open
26(N)
N Common
27(L)
Water Pump 2 (WP2)
28
Aquastat security for circuit 2 (WP2)
29
30(N)
Electrical Heater DHW Output
31(L)
32(C)
Common line
33(L)
3-way valve for DHW tank
34(N)
N common
Output 1 (3-way valve for swimming
35(L)
pool) (*)
36(L)
Output 2 (Water pump 3 (WP3)) (*)
102
PMML0575 rev.2 - 03/2022
The DHW sensor is used to control the temperature of the domestic hot water tank.
Common terminal for thermistor.
The sensor is used for the second temperature control and should be positioned after the mixing
valve and the circulation pump.
Water sensor for hydraulic separator, buffer tank or boiler combination.
Common terminal for thermistors.
The sensor is used for the swimming pool temperature control and should be positioned inside
plate heat exchanger of the swimming pool.
The sensor is used for the second ambient temperature control and it should be positioned
outdoors.
It is possible to connect an external controller to the connector CN5 to provide a manual water
temperature setting. The input current (4-20 mA) will be transformed into voltage by means
of a grounded 240 Ω resistor (ATW-MAK-01 accessory) connected to these terminals. The
DSW5 pin 3 must be in ON position and the SSW1 has to be in Local mode (Enabled manual
operation) to enable this function.
Terminal Line common for input 1 and input 2.
The air to water heat pump system has been designed to allow the connection of a remote
thermostat to effectively control your home's temperature. Depending on the room temperature,
the thermostat will turn the split air to water heat pump system ON and OFF.
Available signal which allows to reduce the water setting temperature of circuit 1, circuit 2 or
both.
Terminal Line common for inputs 3, 4, 5, 6, 7.
Only for swimming pool installations: It is necessary to connect an external input to the air to
water heat pump to provide signal when the water pump of swimming pool is ON.
Available input for Solar combination with Domestic Hot Water Tank.
For the connection of an external tariff switch device to switch OFF the heat pump during peak
electricity demand period. Depending on the setting, the heat pump or DHWT will be blocked
when signal is open/closed.
Available input for an instantaneous heating of the domestic hot water of the tank.
The measuring of the real power consumption can be done connecting an external power meter.
The number of pulses of the power meter is a variable which must be set. By this, every pulse
input is added into corresponding operation mode (Heating, DHW Operation). Two possible
options:
- One power meter for all installation (IU+OU).
- Two separated power meters (one for IU and one for OU).
Terminals intended for the connection of the Aquastat security accessory (ATW-AQT-01) for
controlling water temperature of the circuit 1.
When a mixing system is required for a second temperature control, these outputs are
necessary to control the mixing valve.
When there is a second temperature application, a secondary pump is the circulating pump for
the secondary heating circuit.
Terminals intended for the connection of the Aquastat security accessory (ATW-AQT-01) for
controlling water temperature of the circuit 2.
If DHW tank contains an electric heater, the air to water heat pump can activate it if the heat
pump cannot achieve the required DHW temperature by itself.
Common terminal for the 3-way valve for DHW tank.
The air to water heat pump can be used to heat DHW. This output will be on when DHW is
activated.
Neutral terminal common for 3-way valve of DHW tank and outputs 1 and 2.
The air to water heat pump can be use to heat swimming pool. This output will be ON when
swimming pool is activated.
When there is a hydraulic separator or buffer tank, additional water pump (WP3) is needed.
Description