Refer to IEC 61918 for guidelines regarding conductor sizing and length to prevent a voltage offset
between two communicating devices exceeding 1 V.
Make sure to run the bonding conductor in close proximity to the communication cable.
The Panel PC has a protection ground connection because the metal part of the Panel PC outside of
the enclosure must be part of the protection grounding of that enclosure (for example a cabinet).
There are no power supply voltages used in the Panel PC which require protection grounding.
Ground Connection Details
This section provides details about the ground connection.
Use the ground terminal to ground your Panel PC.
The washers and screw A are pre-mounted at the Panel PC.
Remove the pre-mounted washers and screw A and then mount the ground connection wire C to
the Panel PC B using the washers and screw A .
Tighten the screw with a torque of 1.2 N·m max.
 Crimp terminals
Use crimp terminals with dimensions X = M4 and Y = 8 mm max.
Y X
4-4-2

DC Power Supply

The OMRON S8VK-series power supply is recommended for use with the Industrial Panel PC.
Additional Information
• Refer to 2-5-2 Power Supply on page 2-8 for more information.
• Refer to 3-2-3 Power Consumption Specifications on page 3-6 for power consumption details.
NY-series NYE Industrial Panel PC Conversion Guideline for NS-series products (P157)