Advertisement

5 INSTALLER SETTINGS
No. Installer Setting
8
Cool Setpoint
Upper Limit
Selects the upper setpoint adjustment limit that cannot be exceeded in cool mode.
9
Installer Lock
When enabled, a 4-digit lock code can be entered in setting 10. This lock code will be required the next time the
Installer Settings menu is accessed. Select NO to skip the installer lock.
10
Installer Lock Code
[Only available if Installer Lock was enabled in setting 9] Select a 4-digit lock code (0-9 for each digit) to
lock the Installer Settings menu. The code 0000 is not a valid lock code and cannot be used.
11
Installer Clear
(factory reset)
Selecting Y (YES) will return thermostat to all factory default settings. Factory reset will take affect upon exiting
Installer settings menu.
Additional options are located in the User Settings – See User Manual.
Displayed
Default
Setting
HIGH COOL
90
INST
NO
IL
0000
CLR
NO
Available Description of
Settings
Available Settings
90 - 45 Select a Cool Setpoint Upper Limit of 90° to
(32˚ to 7˚C) 45°F (32° to 7°C)
NO
Installer Lock disabled
Y
Installer Lock enabled
0-9
Select 0-9 for each digit
NO
Clear disabled - No changes made
Y
Clear enabled - Factory Reset
7