Installer Manual
Non-Programmable Thermostats
1030 1 Heat / 1 Cool Conventional
1230 Up to 2 Heat / 1 Cool
1 Specifications
4 Quick Reference 5 Installer Settings 6 System Testing
Warning
For installation by experienced service technicians only.
Caution
Possible electric shock or damage to equipment can occur.
Disconnect power before beginning installation.
This thermostat requires 24 Volt AC Power or 2 properly installed "AA" Alkaline batteries for
proper operation. When connecting 24 Volt AC Power, the batteries may be installed as a backup.
For use only as described in this manual. Any other use will void warranty.
This manual is for Installer use only - do not leave with end user.
1
SPECIFICATIONS
This thermostat is compatible with:
• Single stage conventional and heat pump systems
• Single stage heat pumps with auxiliary heat
• 250 – 750 millivolt heating only systems
• 2 wire hydronic zone systems
Electrical and Control Specifications
• Electrical Rating: 24 Volt AC
• 1 amp maximum load per terminal
• AC Power: 18 – 30 Volts AC
• DC Power: 3.0 Volt DC
(2 "AA" Alkaline Batteries Included)
• Control Range: 45° to 90° F (7° to 32° C)
• Temperature Accuracy: +/- 1° F (+/- .5° C)
or Heat Pump
Conventional or Heat Pump
Model number is located on back of thermostat.
2 Installation
®
3 Wiring
Terminations
1030: Rc, Rh, W1, Y1, G, O, B, C
1230: Rc, Rh, W1/E, W2, Y1, G, O, B, L, C