Water Connection - Orca ZEUS ZSW 230 Installation, Maintenance And User Manual

Domestic hot water heat pump
Hide thumbs Also See for ZEUS ZSW 230:
Table of Contents

Advertisement

User manual

12 WATER CONNECTION

The cold-water connection must be performed according to the scheme above. The maximum allowed
pressure in the water system is 0,4 MPa, a safety valve with a maximum pressure 0,6MPa can be used.
Expansion vessel for the 230L tank needs to have at least 12L volume and for the 300L tank 18L.
Hot water connection can be directly to tap, or can be upgraded with a circulation pump. Return from the
circulation system can be connected to the connection marked with "E" in scheme "10. Unit dimensions".
During rapid water heating, a small water leakage on the safety valve can occur. This is not due to damage but
due to normal event of water expansion. This water needs to be captured and lead into drainage.
In case of a solar system or other heat source connected to the internal heat exchanger, it must be assured
that the pressure in the heat exchanger newer exceeds 0,5MPa. It must also be assured that the water does
not exceed 80°C. Damage to internal components or heat pump can occur.
In case that the additional heat exchanger is not to be used, it needs to be filled with glycol to prevent
corrosion. It is not allowed to close both sides of the heat exchanger to enable pressure equalization.
WARNING!
Improper installation of the unit can lead to damages or malfunction of the unit and loss of rights
under warranty.
WARNING!
Connect the unit to the system using removable pipe unions, so that the unit can be easily moved or
removed in case of a service intervention without the need of a greater intervention in the piping
system.
WARNING!
When connecting the unit to the heating system it is necessary to prevent the formation of a
galvanic couple and related corrosion. To connect the unit to the heating system it is MANDATORY
to use the enclosed transition pieces, also the piping system MUST be electrically grounded. In case
of failure due to improper device connection the manufacturer will take no liability or warranty.
WARNING!
Before the unit is turned on, it needs to be filled with water and the system completely vented. To
do this, open all hot water taps and wait until water starts to flow from all of them.
WARNING!
On the back side of the unit there is a pipe connection for condensate drain. At high water usage
and high air humidity, more than a few litres of condensate water per day can occur, so this
connection must be connected to outlet drainage. This pipe needs to have a constant incline of at
least 1° and must be always clean.
12
ZEUS

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zeus zsw 300

Table of Contents