USB Interface
This interface is reserved for future use.
Local Port
Software
EasyView software is a Windows-compatible communications package designed specifically for use
with Galaxy controllers. Download EasyView software from abbpowerconversion.com
Wiring Alarm Outputs
These external alarms may be wired to customer external office alarms at their destination.
Form-C Alarm Contact Ratings
Conductor Size for terminating on Alarm board
Refer to Table 4-B and 4-C for lead designations and their descriptions for leads terminating on the
BSL alarm interface board.
Pin Number
Signal Name
1
PCRAO
2
PCRAC
3
PCRAR
4
PCRVR
5
PCRVC
6
PCRVO
7
PCREO
8
PCREC
Page 43
© Copyright 2021 ABB. All rights reserved.
60Vdc, 0.3A
18 – 22AWG (if less than 18AWG, use multi-conductor cable for
mechanical integrity)
Pin Number
Signal Name
33
MJFR
34
MNFR
35
MNFC
36
MNFO
37
BDO
38
BDC
39
BDR
40
ACFR
Table 9-B Controller Alarm Descriptions and Pin Numbers
Pin Number
Signal Name
65
FAN
66
AMN
67
TFLT
68
TBST
69
TRTN
70
PBTR
71
PBT
72
OS