Download Print this page

ABB REL 352 Instruction Manual page 89

Numerical phase comparison transmission line protection system

Advertisement

Power Automation and Protection Division
Schematic - - - - - - - - - - - - - - 1611C36
Component Location Diagram - - - - 1611C27
There are 3 versions of the Relay Output module for each operating voltage (48, 125 and 250 Vac), as follows:
Version
• Option
• Base 1
• Base 2
The option version provides phase B and C control functions for Single Pole Trip (SPT).
All 9 version/voltage variants share components of the same PC Board; the slight differences are shown on
1611C27 (sheet 1). The 3 versions are plugged-in and permanently secured (via brackets) to the following con-
nectors on the Interconnect module.
Version
• Option
• Base 1
• Base 2
Connector JB connects (via the Interconnect module) to the Microprocessor module's digital I/0 interface.
Connector JA connects relay contacts through the Backplane module to the outside world.
Opto-isolators U1, U2, U3 and U4 interface logic level output signals from the Microprocessor module to relay
driver transistors (Q1 through Q4, respectively).
Output relays K1, K2, K5, K6, K9, K10 provide desired control operations. Reed relays K3, K4, K7, K8 monitor
the breaker trip control circuit current.
Connector terminals are assigned the following functions ( see Table C-1 ):
Option
Terminal
Version
JB-8A
Reed B2
Reed A2
JB-6A
Reed B1
Reed A1
Trip A (3Ø)
JB-2A
Trip B
JB-6C
Reed C2
JB-8C
Reed C1
JB-2C
Trip C
GS (Gen. Start)
JB-4A
BFIB
BFIA
JB-4C
BFIC
RB
REL 352 Version 1.00
RELAY OUTPUT MODULE
Function
Trip, Breaker Failure
Trip, Breaker Failure, General Start, Reclose Blocking
Trip Alarm, Failure Alarm, Reclose Initiate
Interconnect Module Connector
JB1
JB2
JB3
Table C-1:
Base 1
Base 2
Version
Version
Trip Alarm
Failure Alarm
RI1
RI2
Option
Terminal
Version
JA-30AC/28AC
Trip B1
Trip A(3Ø) - 1
JA-26AC/24AC
Trip B2
Trip A(3Ø) - 2
JA-22AC/20AC
Trip C1
JA-18AC/16AC
Trip C2
GS
JA-14AC/12AC
BFIB-1
BFIA-1
JA-10AC/8AC
BFIB-2
BFIA-2
JA-6AC/4AC
BFIC-1
RB-1
JA-2A/2C
BFIC-2
RB-2
I.L. 40-201.9
Base 1
Base 2
Version
Version
Trip Alarm -1
Trip Alarm -2
Failure Alarm
RI1-1
Ri1-2
RI2-1
RI2-2
C-1
A
P
P
E
N
D
I
X
C

Advertisement