ABB REL 352 Instruction Manual page 144

Numerical phase comparison transmission line protection system

Advertisement

Power Automation and Protection Division
The following are external reverse faults.
The system should not trip.
8.2.
Phase-to-phase Unit
To calculate the apparent impedance seen by the relay for phase-to-phase faults the following formula applies:
Vxy
------------- -
Zapp =
Ix
Iy
where x is phase a, b or c and y is the next lagging phase.
The above formula is rigorous and general. However, if a quick approximation of the current required at different
angles (Ø) is desired, the following formula applies:
V
XY
I
=
---------------------------------------------------------- -
(
(
Pang φ
2 Z 2P
cos
The phase-to-phase unit is totally directional. For forward Zone 2 trips the following quantities should be ap-
plied:.
REL 352 Version 1.00
V
AG
Va = 25 ∠0
Vb = 69 ∠-120
Vc = 69 ∠+120
BG
Va = 69 ∠0
Vb = 25 ∠-120
Vc = 69 ∠+120
CG
Va = 69 ∠0
Vb = 69 ∠-120
Vc = 25 ∠+120
)
)
V
AB
Va = 35 ∠0
Ia = 10 ∠-45
Vb = 35 ∠-120
Ib = 10∠+135
Vc = 69 ∠+120
Ic = 0
BC
Va = 69 ∠0
Ia = 0
Vb = 35 ∠-120
Ib = 10∠-165
Vc = 35 ∠+120
Ic = 10∠+15
CA
Va = 35 ∠0
Ia = 10∠-105
Vb = 69 ∠-120
Ib = 0
Vc = 35 ∠+120
Ic = 10∠+75
I
Ia = 3.75 ∠+105
Ib = 0
Ic = 0
Ia = 0
Ib = 3.75∠-15
Ic = 0
Ia = 0
Ib = 0
Ic = 3.75∠-135
I
Z app
3.08∠75
3.08∠75
3.08∠75
I.L. 40-201.9
A
P
P
E
N
D
I
X
I
I-7