Setting
Format
VERS
XX.XX
FREQ
50/60
RP
YES/NO
CTYP
XXXX
CTR
XX.XX
VTR
XXXX
OSC
TRIP/ITRG/∆V∆I
FDAT
TRIP/ITRG
TRGG
XX.XX
TRGP
XX.XX
∆I/∆V ∆I
CD
RBEN
NORB/ALRB
UNBK
IN/OUT
CNT
1CNT/2CNT
ARMT
0/150
LP
XX.XX
FD2
XX.XX
IPLT
XXXX
IPL
XX.XX
IPH
XX.XX
IGH
XX.XX
IKEY
XX.XX
TERM
2TRM/3TRM
COMM
2ST/3ST
CINT
(later)
C0
X.XX
C1
X.XX
C2
X.XX
LDT1
XXX.X
LDT2
XXX.X
LPBK
YES/NO
XPUD
X.XXX
DTYP
MI/KM
PANG
XXXX
GANG
XXXX
ZR
XXX.X
BKUP
IN/OUT
LOPB
YES/NO
FDOP
IN/OUT
FDOG
IN/OUT
DIRU
ZSEQ/NSEQ
IOM
XX.XX
TOG
XX.XX
REL 352 Version 1.00
TABLE 4-4. SETTING INFORMATION
Min
Max
0.01
99.99
1
5
30
5000
300
7000
0.1X I
2.0 X I
n
n
0.1X I
2.0 X I
n
n
0.04 XI
2.0 X I
n
n
0.04 X I
2.0 X I
n
n
0
150
0.1 X I
0.8 X I
n
n
0.8 X I
16.0 X I
n
n
0.8 x I
16.0 X I
n
n
0.04 X I
2.0 X I
n
n
0.00
5.00
0.00
5.00
0.00
5.00
0
32.0
0
32.0
0.300
1.500
40
90
40
90
0.1
7.0
2.0 X I
0.1 X I
n
n
0.10
9.99
Step
Units
Hz
4
Amp
5
10
0.1 X I
Amps
n
0.1 X I
Amps
n
0.02 X I
Amps
n
0.02 X I
Amps
n
150
msec
0.02 X I
Amps
n
0.02 X I
Amps
n
0.02 X I
Amps
n
0.02 X I
Amps
n
0.05
0.05
0.05
0.1
msec
0.1
msec
0.001
ohms/DTYP
1
deg
1
deg
0.1
0.02 X I
Amps
n
0.01
sec
I.L. 40-201.9
Notes
CTYP = I
n
1
4
1
1
1
1
1, 3
1, 3
1
1
1
1
2
4-15