Download Print this page

ABB REL 352 Instruction Manual page 55

Numerical phase comparison transmission line protection system

Advertisement

I.L. 40-201.9
4.4.1.1
Relay Output Test
All relay outputs can be tested using the procedure
described below:
(1) Open the FT switch, using the red handles of
the breaker trip circuits, making sure that the
following jumper is not disturbed:
BFI/RECLOSE ENABLE
(2) Install jumper JMI in position 1-2 on the Micro-
processor module.
(3) Continually depress the "DISPLAY" key until
the "TEST" LED is illuminated; then depress
the "FUNCTION RAISE" or "FUNCTION LOW-
ER" key until the words "TRIP" and "RELY"
appear in the FUNCTION and VALUE fields,
respectively.
(4) Activate the "ENTER" key for the desired dura-
tion of the output relays operation.
(5) Depress the "FUNCTION RAISE" key to select
the following parameters, as desired:
TRIP
BFI
SRI (RI1-1,2)
3RI (RI2-1,2)
RB
GS
FALM
TALM
CALM
NOTE:
(6) After completion of this test, restore the system to its operating state by moving JM1 to po-
sition 2-3 on the Microprocessor module, and closing the FT switch red handles.
4.4.2. Self Check
The results of the system self-check routines are accessible using the following procedure:
a. Continually depress the "DISPLAY" key until the "TEST" LED is illuminated; then depress
the "FUNCTION RAISE" or "FUNCTION LOWER" key until the word "STAT" appears in the
FUNCTION FIELD.
b. The VALUE FIELD will display the status of the relay in hexadecimal Format:
4-6
FUNCTION
FIELD
Activate the "ENTER" key to operate selected output relays.
Power Automation and Protection Division
Binary-to-Hexadecimal Conversion
BIT NUMBER
3/7
2/6
0
0
0
0
0
0
0
0
0
1
0
1
0
1
0
1
1
0
1
0
1
0
1
0
1
1
1
1
1
1
1
1
VALUE
FIELD
RELY
RELY
RELY
RELY
RELY
RELY
RELY
RELY
RELY
Table 4-2:
1/5
0/4
HEX DIGIT
0
0
0
0
1
1
1
0
2
1
1
3
0
0
4
0
1
5
1
0
6
1
1
7
0
0
8
0
1
9
1
0
A
1
1
B
0
0
C
0
1
D
1
0
E
1
1
F
DESCRIPTION
TRIP (A, B, C)
Breaker Failure Initiate
Reclose Initiate
Reclose Initiate
Recloser Blocking
General Start
Failure Alarm
Trip Alarm
Channel Alarm
REL 352 Version 1.00