ABB REL 352 Instruction Manual page 81

Numerical phase comparison transmission line protection system

Advertisement

Power Automation and Protection Division
Schematic - - - - - - - - - - - - - - - - - - - - - 1612C22
Component Location Diagrams - - - - - - 1611C26, 1502B38
All external electrical connections pass thru the Backplane module (see Figure 4-1) of the outer chassis. Seven
DIN connectors (J11, J12, J13, JA1, JA2, JA3 and JA4) allow for the removal of the outer chassis (Backplane
module) from the inner chassis (Interconnect module, Contact Input and Relay Output modules).
Electrical inputs to the Backplane module, which are routed through the FT-14 switch to the Backplate, include:
The Backplane module, (see Figure A-1 and Schematic) contains three voltage-type transformers, for V
(V
), V
/V
(V
), V
/V
AN
B
N
BN
C
N
A Transformer module (see Figure A-2 and Schematic) is piggybacked onto the Backplane module, consisting
of three current-type transformers (I
ers are directly-connected to the input terminal (TB6/1
the Interconnect module to the Analog Input module. The current transformers (I
offset attenuation is done with a digital filtering algorithm. Surge suppression is included where the signals enter
the module.
The Backplane module also includes:
INCOM/PONI is supplied in two versions:
REL 352 Version 1.00
BACKPLANE MODULE
V
, V
, V
, and V
A
B
C
N
I
/I
, I
/I
, I
/I
A
AR
B
BR
C
CR
BP(48, 125 or 250 Vdc) and BN (common) for primary and backup power inputs.
(V
) inputs.
CN
, I
, I
) with three 0.1% resistors. The primary windings of all six transform-
A
B
C
4 chokes (L1 thru L4) for dc power supply filter
surge-suppressor capacitors
INCOM/PONI to RS232 computer interface (supplied as standard).
INCOM/PONI to INCOM network interface (supplied as option).
thru 10); the secondary windings are connected thru
, I
A
I.L. 40-201.9
/V
A
N
, I
) are not gapped; dc
B
C
A-1
A
P
P
E
N
D
I
X
A