Add energy meter
rd
The energy meter needs to be manually added which is same as any other 3
party
equipment.
To add the energy meter, click 'Add device' and select a device type in the pop-up
window and fill in the required information (Add device for DTSD1352 energy meter
and device address: 254)
If the energy meter's status (DTSD1352) is disconnected on the portal, please
double check the com port number. Take the following figure as a sample, if the
meter connected with A2 and B2 on the Logger1000, we need to make sure the port
number on the portal is com2. Otherwise, it will show disconnect.
Go into the settings to select the grid standard and any other variations or protection
parameters.
Individual inverters can be accessed by clicking on the inverter serial number.
Add CT Transformation Ratio.
If the ratio is 200/5, then enter value 40.
TD_202005_Logger1000_Quick Guide for SG30-50-110CX Inverters_V1.3