ALARM MENU

The ALARM menu is used to view (and reset, if necessary) the alarm conditions that
may arise on the unit while it's working. The alarms are divided into various catego-
ries according to their seriousness. Remember that some of them can cause serious
damage to the unit so, before performing a reset, it's important to be sure about the
nature of the alarm and the reason it was triggered (contacting specialised techni-
cal personnel if necessary).

5.1 DISPLAYS ACTIVE ALARMS

— Indicates the currently active alarm number
— Indicates the total number of alarms currently active on the system
— Indicates the code of the currently active alarm
— Indicates the description of the currently active alarm
Go to alarms log
Reset
— Holding this key
for a few seconds resets the currently active alarm dis-
played (if the alarm includes a manual reset)

5.3 LIST OF ALARMS

Each alarm can have a specific type of reset, these types can be:
Auto (automatic) = the alarm disappears when the event which generated it ceas-
es;
Man (manual) = to resume normal operation, manual recognition by an operator
is required (via a touch screen or BMS);
Semi (semi-automatic) = the alarm is automatic, but if it is triggered more than 3
times in an hour then it becomes with manual reset;
Code
AL001
AL002
AL003
AL004
AL005
AL006
AL007
AL008
AL009
AL010
AL011
AL012
AL013
AL014
AL015
AL016
AL017
AL018
AL019
AL020
AL021
AL022
AL023
AL024
AL025
AL026
AL027
AL028
AL029

5.2 DISPLAYS ALARMS LOG

— It indicates the alarm number within the log (the log contains a maximum of
100 alarms, after which it saves the next ones overwriting the oldest ones)
— Date and time fo the alarm
— Alarm code and description
— Collection of the operating parameters of the unit recorded when the alarm
was generated
TurboAL = characteristic alarm of Turbocor compressors. It is automatically reset
with the following procedure:
1. Turn off the affected compressor removing request;
2. Wait for a time of 30s (settable);
3. 10% power is given to the TurboCor;
4. The Turbocor resets the alarm;
5. The TurboCor repositions the IGV valve (approximately 120 s);
6. The pCO can turn on the TurboCor compressor again;
Description
From digital input
Phase or voltage monitor
Evaporator Anti-freeze
Compressor 1 circuit breaker
System Flow Meter
From digital input, EEV
Pressure Switch high pressure
Transducer High pressure
Pressure Switch low pressure
Transducer low pressure
Critical low pressure
Fan/condenser pump circuit breaker
System pump 1 circuit breaker
System pump 2 circuit breaker
System pump 1 maintenance
System pump 2 maintenance
Compressor 1 Maintenance
Compressor 2 Maintenance
Probe U1 broken or disconnected
Probe U2 broken or disconnected
Probe U3 broken or disconnected
Probe U4 broken or disconnected
Probe U5 broken or disconnected
Probe U6 broken or disconnected
Probe U7 broken or disconnected
Probe U8 broken or disconnected
Probe U9 broken or disconnected
Probe U10 broken or disconnected
Turbocor1 Pressing line Gas High Temp.
Reset
Auto
Auto (sw>=2.2.3)
Manual
Manual
Manual
Auto
Manual (password)
Manual
Manual (password)
Manual
Manual
Manual
Manual
Manual
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Manual
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Turbocor pco5

Table of Contents