4.2. CIRCUIT BOARD ERROR CODE
4.3. FACTORY RESET
1. Disable power charge .
2. Press and hold down both the [-] and [+] button on the circuit board
and switch on the power again. The blue LED will light up, followed
by the green LED 2 seconds later and the red LED 4 seconds later.
Release the buttons as soon as all 3 LEDs are flashing
3. The controller will return to the Factory Default settings, all LEDs will
flash for 8 seconds .
JAGA N.V. | DBH SET - BMS | MANUEL | 2021.08.23 | V.01
Check the water temperature sensor
Check the room temperature sensor
-
EN
33