How to reset the fire thermostat

Fire thermostat
Procedure
8
The fire thermostat is an on/off function. A signal is given to the control if
• the air inlet temperature is higher than the pre-set temperature, e.g. + 70 °C
or
• the extract air temperature is higher than the pre-set temperature, e.g. + 40 °C
If the unit is delivered with control from Dantherm Air Handling, the release of the fire
thermostat will switch off the ventilation unit.
Do as follows to reset the fire thermostat:
Step
1
Localize the fire thermostat which may be placed either
• in the return air at the top of the heat exchanger module or
• in the supply air duct
2
Press the red button to reset the fire thermostat