Generator Main Line Circuit Breaker (Generator Disconnect); Parts Shipped Loose; Auxiliary Shutdown Switch - Generac Power Systems PWRgenerator 9 kW Installation Manuallines

Air-cooled generator
Hide thumbs Also See for PWRgenerator 9 kW:
Table of Contents

Advertisement

Unpacking and Inspection
Generator Main Line Circuit Breaker
(Generator Disconnect)
See
Figure
2-9. The 2-pole main line circuit breaker
(MLCB) (generator disconnect) (A) is rated according to
relevant specifications.
B
A
Figure 2-9. Generator Main Line Circuit Breaker
(MLCB)
Generator MLCB (generator disconnect) can be locked in
OFF (OPEN) position for security during maintenance.
Use an appropriately-sized padlock (not included) with a
shackle long enough to pass through both lock tabs (B).
NOTE: DO NOT leave generator MLCB (generator dis-
connect) locked in the open (OFF) position during normal
generator operation. Leaving the generator MLCB (gen-
erator disconnect) in OFF (OPEN) position will prevent
generator from powering structure when placed in AUTO
mode.

Parts Shipped Loose

A
A
Keys
B
Flexible fuel line
C
Battery terminal cap
D
Decal—Service entrance warning (not shown)
E
Owner's and Installation manuals (not shown)
Figure 2-10. Parts Shipped Loose
10
001810
C
B

Auxiliary Shutdown Switch

Equipment Damage. The auxiliary shutdown switch
is not to be used to power down the unit under
normal operating circumstances. Doing so will
result in equipment damage.
All generators are equipped with an external means of
shutting down the generator which complies with the lat-
est NEC code requirement. The primary generator shut-
down sequence is described in
Testing.
See
Figure
2-11. An auxiliary shutdown switch is pro-
vided on the exterior of the generator back panel. This
switch shuts down the generator and disables restarts.
001810
Figure 2-11. Auxiliary Shutdown Switch
NOTE: Whenever possible, perform primary shutdown
procedure before disabling generator with auxiliary shut-
down switch.
Generator will not start if auxiliary shutdown switch is
OPEN (O). Controller displays an "Auxiliary Shutdown"
alarm, and red LED "Alarm" light illuminates until auxiliary
shutdown switch is CLOSED (I) and alarm is cleared by
pressing OFF mode button, and then ENTER. Once
cleared, generator can be placed back in AUTO or MAN-
UAL.
013415
Installation Guidelines for PWRgenerator Air-Cooled Generators
CAUTION
(000399)
Control Panel Startup /
013416