Generac Power Systems PWRgenerator 9 kW Installation Manuallines page 46

Air-cooled generator
Hide thumbs Also See for PWRgenerator 9 kW:
Table of Contents

Advertisement

Quick Reference Guide
Active Alarm
LED
OVERVOLTAGE
RED
AUXILIARY
RED
SHUTDOWN
LOW BATTERY
YELLOW
BATTERY
YELLOW
PROBLEM
CHARGER
YELLOW
WARNING
LOW REBUS
VOLTAGE
YELLOW
WARNING
LOW REBUS
VOLTAGE
YELLOW
WARNING
SERVICE A
YELLOW
SERVICE B
YELLOW
INSPECT
YELLOW
BATTERY
44
Problem
Unit will not start in AUTO
with utility loss.
Unit will not start.
Yellow LED illuminated in
any state.
Yellow LED illuminated in
any state.
Yellow LED illuminated in
any state.
Yellow LED illuminated in
any state.
Yellow LED illuminated in
any state.
Yellow LED illuminated in
any state.
Yellow LED illuminated in
any state.
Yellow LED illuminated in
any state.
Actions
Check LED's / Screen
Contact an IASD.
for alarms.
Check auxiliary
Set auxiliary shutdown switch(es) to
shutdown switch(es).
CLOSED (I).
Clear alarm. Using control panel, check
battery by navigating to BATTERY MENU
Check screen for
option from MAIN MENU. If battery condi-
additional information.
tion displays GOOD, contact an IASD. If
control panel displays CHECK BATTERY,
replace battery.
Check screen for
Contact an IASD.
additional information.
Check screen for
Contact an IASD.
additional information.
Check screen for
Contact an IASD.
additional information.
Set generator MLCB (generator
Check screen for
disconnect) to ON (CLOSED). Contact an
additional information.
IASD if issue persists.
Check screen for
Perform SERVICE A maintenance. Press
additional information.
ENTER to clear.
Check screen for
Perform SERVICE B maintenance. Press
additional information.
ENTER to clear.
Check screen for
Inspect battery. Press ENTER to clear.
additional information.
Installation Guidelines for PWRcell Air-Cooled Generators
Solution