Operation
NOTE: See
Figure
3-10. Remove front and intake pan-
els from unit, and remove 15A fuse (A) from converter.
Figure 3-10. 15A Fuse Location
To turn generator back ON:
NOTE: Install 15A fuse and enclosure panels if mainte-
nance was performed.
1. Install 7.5A fuse in controller.
2. Complete Install Wizard.
3. Verify generator MLCB (generator disconnect) and
PWRcell Inverter DC disconnect circuit breaker are
OFF (OPEN).
4. Set generator to AUTO mode at the controller.
5. Set PWRcell Inverter DC disconnect circuit breaker
to ON (CLOSED).
6. Set generator MLCB (generator disconnect) to ON
(CLOSED).
The system now operates in automatic mode.
DO NOT leave generator MLCB (generator disconnect)
in OFF (OPEN) with 7.5A fuse installed for more than two
hours or starter battery will discharge.
20
A
014082
Owner's Manual for PWRgenerator Air-Cooled Generators