Quick Reference Guide

To clear an active alarm, press OFF button on the control panel, then the ENTER button, and finally the AUTO button.
Contact an IASD if alarm reoccurs.
Active Alarm
LED
FLASHING
NONE
GREEN
HIGH
RED
TEMPERATURE
OVERLOAD
RED
REMOVE LOAD
RPM SENSE LOSS
RED
NOT ACTIVATED
NONE
NONE
GREEN
NONE
GREEN
LOW OIL
RED
PRESSURE
RPM SENSE LOSS
RED
OVERCRANK
RED
LOW VOLTS
RED
REMOVE LOAD
OVERSPEED
RED
UNDERVOLTAGE
RED
UNDERSPEED
RED
Owner's Manual for PWRgenerator Air-Cooled Generators
Problem
Unit running in AUTO
but no power in house.
Unit shuts down during
Check LEDs / screen
operation.
Unit shuts down during
Check LEDs / screen
operation.
Unit was running and
Check LEDs / screen
shut down, attempts to
restart.
Unit will not start in
Check if screen says
AUTO with utility loss.
Check HOME screen
on PWRcell Inverter
Unit will not start in
control panel for PV
AUTO with utility loss.
production and export
Unit will not start in
Check screen for start
AUTO with utility loss.
Unit will not start in
Check LEDs / screen
AUTO with utility loss.
Unit will not start in
Check LEDs / screen
AUTO with utility loss.
Unit will not start in
Check LEDs / screen
AUTO with utility loss.
Unit will not start in
Check LEDs / screen
AUTO with utility loss.
Unit will not start in
Check LEDs / screen
AUTO with utility loss.
Unit will not start in
Check LEDs / screen
AUTO with utility loss.
Unit will not start in
Check LEDs / screen
AUTO with utility loss.
Troubleshooting / Quick Reference Guide
Action
Check generator
Check generator MLCB (generator
MLCB (generator
disconnect). If it is ON, contact an IASD.
disconnect).
Inspect ventilation around generator,
intake, exhaust, and rear of generator. If
for alarms.
no obstructions are present, contact an
IASD.
Clear alarm and remove household loads
for alarms.
from generator. Put in AUTO and restart.
Clear alarm and remove household loads
from generator. Put into AUTO and
for alarms.
restart. If generator does not start, contact
an IASD.
See Activation in installation manual.
unit not activated.
Batteries and/or solar are providing
power.
from PWRcell
Batteries.
If startup delay is greater than expected,
contact an IASD to adjust from 2 to 1500
delay countdown.
seconds.
Check oil level and add oil as needed. If
for alarms.
oil level is correct, contact an IASD.
Clear alarm. Using control panel, check
battery by navigating to BATTERY MENU
option from MAIN MENU. If battery condi-
for alarms.
tion displays GOOD, contact an IASD. If
control panel displays CHECK BATTERY,
replace battery.
Verify fuel line shutoff valve is ON. Clear
alarm. Start unit in MANUAL. If it does not
for alarms.
start, or starts and runs rough, contact an
IASD.
Clear alarm and remove household loads
from the generator. Put in AUTO and
for alarms.
restart.
Contact an IASD.
for alarms.
Contact an IASD.
for alarms.
Contact an IASD.
for alarms.
Solution