TR OUB LESHOOT IN G A ND MA INT ENA NCE
Problem
No communica-
tion between DCS
and Digital Gate-
way
Table 26 Digital Gateway Troubleshooting
1 TG C90 80 04
Solution
Check if cable connection, shielding, and termination are all in line with the
requirements of Profibus standard.
Check if slave address settings are correctly parameterized in MNavigate
and the parameters have been downloaded to the Digital Gateway. Ensure
correct settings and no double addressing in the PROFIBUS network
Check if master configuration in the DCS, please check the correct GSD file is
being utilized, and the correct node is being addressed.