Modbus Parameters - ABB CoreSense M10 User Manual

Multi-gas monitoring system
Hide thumbs Also See for CoreSense M10:
Table of Contents

Advertisement

Modbus parameters

NOTICE
Only read-only holding registers are supported in this implementation.
The Modbus slave ID is 1.
Register
Modbus
number
0
1-10
11-20
40011
Model number
21-30
40021
Serial number
31-40
40031
SW revision
41-50
40041
System id
51
40051
Manufacturing date
52
40052
53
40053
System status
54
40054
FGS status
55
40055
Moisture status
56
40056
Moisture (aw)
57
40057
Moisture (ppm)
58
40058
Moisture RoC (ppm/day)
59
40059
ReSeRVed–Moisture RoC
(ppm/week)
60
40060
ReSeRVed–Moisture RoC
(ppm/month)
61
40061
Hydrogen status
62
40062
Hydrogen (ppm)
63
40063
Hydrogen RoC (ppm/day)
A54 User Guide
Parameter
Reserved
not supported
Reserved
info
high byte =
month
low byte =
day
Year
System status
see <Status>
table
internal error
dissolved gas and moisture
scaled by
1000
return 0
return 0
Function
Datatype
ASCii string
ASCii string
ASCii string
ASCii string
32-bit binary value
16-bit binary map
signed 16-bit binary number
16-bit binary map
signed 16-bit binary number
signed 16-bit binary number
signed 16-bit binary number
signed 16-bit binary number
signed 16-bit binary number
16-bit binary map
signed 16-bit binary number
signed 16-bit binary number
DataRange
see <Status>
table
ABB service
see <Gas
status> table
see <Gas
status> table