A p p e n d i x B
DNP3
The CoreSense M10 DNP3 outstation implementation is compliant to level 1 and level 2. You can
communicate with the sensor using a data link address = 1. DNP3 is available on the RS-485 serial
interface or on the Ethernet interfaces.
NOTICE
For best results, it is recommended to configure the DNP3 master with a time out of
10000 ms and 5 retries.
Minimum delay between polls shall be at least 100 ms.
The DNP3 cold restart function is not supported for cybersecurity reasons.
The outstation ID is 1.
RS-485 configuration
Baud rate
data Bits
Stop bits
parity
Flow control
TCP configuration port
dnp3
9600
8
1
none
none (only none is supported)
20.000