Configuring alarms and warnings for gas level events

The CoreSense M10 multi-gas monitoring system is delivered with preset gas level event warnings
and alarms. It is possible to modify these default presets. The system supports two user-configurable
thresholds for level alarms and two additional user-configurable thresholds for rate-of-change alarms.

Level

Default warning and alarm thresholds can be modified. It is your responsibility to define warning and
alarm thresholds suited to your transformer condition and application.
To configure these settings:
1 From the CoreSense M10 dashboard, click Settings. The Settings page appears.
2 Click Sensors settings and enter your password when asked. The Gas Sensors Settings page
appears.
3 Click the arrows adjacent to DGA and fgs. A list of all sensor-measured values appears.
Figure 23 Entering post-processing values
4 Select the value or gas whose events you want to configure (ten gases, oil temperature and TDCG
[total dissolved combustible gas]).