Toshiba RAV-HM561UTP Series Service Manual page 90

Split type indoor unit 4-way cassette type
Table of Contents

Advertisement

CODE No.
Data name
Room temperature
01
(Remote controller)
02
Indoor suction temperature (TA)
Indoor heat exchanger (Coil)
03
temperature (TCJ)
Indoor heat exchanger (Coil)
04
temperature (TC)
07
Indoor fan revolution frequency
Communication protocol
B9
0000: TCC-LINK, 0001: TU2C-LINK
F2
Indoor fan calculated operation time
F3
Filter sign time
Indoor unit discharge air temperature
F8
(TF) *1
Secondary heating output
E5
- - - - : Unavailable
0000 : OFF, 0001 : ON
Free cooling output
E6
- - - - : Unavailable
0000 : OFF, 0001 : ON
Rotation operation
- - - - : Unavailable
E9
0000 : Rotation operation OFF
0001 : Rotation operation ON, Unit ON
0002 : Rotation operation ON, Unit OFF
*1 : The above temperature values are estimated from the temperature of the heat exchanger. It may differ from
the actual discharge temperature.
*2 : For outdoor unit data, refer to the Installation Manual and Service Manual of the outdoor unit.
Unit
CODE No.
60
Outdoor heat exchanger (Coil) temperature (TE)
°C
61
Outside temperature (TO)
°C
62
Compressor discharge temperature (TD)
63
Compressor suction temperature (TS)
°C
65
Heat sink temperature (TH)
°C
6A
Operation current (× 1/10)
6D
Outdoor heat exchanger (Coil) temperature (TL)
rpm
70
Compressor operation frequency
72
Outdoor fan revolution frequency (Lower)
73
Outdoor fan revolution frequency (Upper)
×100h
F1
Compressor calculated operation time
×1h
°C
- 90 -
Data name
Unit
°C
°C
°C
°C
°C
A
°C
rps
rpm
rpm
×100h