Toshiba RAV-HM561UTP Series Service Manual page 80

Split type indoor unit 4-way cassette type
Table of Contents

Advertisement

<RBC-AMTU3∗ ∗ ∗ ∗ ∗ >
1. When pushing
button on the remote controller for 4 seconds or more, "TEST" is displayed on LC display.
Then push
button.
• "TEST" is displayed on LC display during operation of Test Run.
• During Test Run, temperature cannot be adjusted but air volume can be selected.
• In heating and cooling operation, a command to fix the Test Run frequency is output.
• Detection of trouble is performed as usual. However, do not use this function except case of Test Run
because it applies load on the unit.
2. Use either heating or cooling operation mode for [TEST].
NOTE : The outdoor unit does not operate after power has been turned on or for approx. 3 minutes after
operation has stopped.
3. After a Test Run has finished, push
(To prevent a continuous test run operation, 60-minutes timer release function is provided to this remote
controller.)
<Wireless remote controller>
1
Turn on the power of the air conditioner.
When power is turned on for the first time after installation, it takes approx. 5 minutes until the remote
controller becomes available. In the case of subsequent power-on, it takes approx. 1 minute until the remote
controller becomes available.
Execute a test run after the predetermined time has passed.
2
Push "ON/OFF" button on the remote controller, select [
then select [
3
Cooling test run
Set the temperature to 17 °C
with the temp. setup buttons.
4
Cooling test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 18 °C with
the temp. setup buttons.
5
Cooling test run
After confirming a signal
receiving sound "beep"
Immediately set the
temperature to 17 °C with
the temp. setup buttons.
6
4
Repeat procedures
Indicators "Operation" (green), "Timer" (green), and "Ready" (orange) in the wireless receiver section flash
in approx. 10 seconds, and the air conditioner starts operation. If any of these indicators does not flash,
repeat procedures 2 to 5.
7
Upon completion of the test run, push "ON/OFF" button to stop operation.
button again and check that [TEST] on LC display has gone off.
HIGH ] with "FAN" button.
Heating test run
Set the temperature to 30 °C
with the temp. setup buttons.
Heating test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 29 °C with
the temp. setup buttons.
Heating test run
After confirming a signal
receiving sound "beep"
immediately set the
temperature to 30 °C with
the temp. setup buttons.
5
4
5
.
→ → → → →
→ → → → →
→ → → → →
Cool ] or [
- 80 -
Heat ] with "MODE" button, and

Advertisement