Fujitsu AUXG07KVLA Manual page 319

2-unit multi-split type
Hide thumbs Also See for AUXG07KVLA:
Table of Contents

Advertisement

 Heating operation
Switch the airflow AUTO, and the indoor fan motor will run according to a room temperature, as be-
low.
On the other hand, if switched in HIGH—QUIET, the indoor motor will run at a constant airflow of
HEAT operation modes QUIET, LOW, MED, HIGH as shown in "Fan speed" above.
Airflow change over (Heating: Auto)
-1°C
> Tr - Ts ≥
 Cool air prevention control (heating mode)
The maximum value of the indoor fan speed is set as shown below, based on the detected tempera-
ture by the indoor heat exchanger sensor on heating mode.
• Normal operation
13 minutes later:
3-1. Indoor fan control
When the room
temperature rises
Tr - Ts ≥
-1°C
LOW mode
-2°C
MED mode
-2°C > Tr - Ts
HIGH mode
Indoor heat exchanger
temperature rises
HIGH
or setting fan mode*
42°C
MED+
or setting fan mode*
39°C
LOW
or setting fan mode*
37°C
Cool air prevention
30°C
*: Lower speed is selected.
Indoor heat exchanger
temperature rises
HIGH
or setting fan mode*
42°C
MED+
or setting fan mode*
39°C
LOW
or setting fan mode*
37°C
LOW
or setting fan mode*
30°C
LOW
or setting fan mode*
*: Lower speed is selected.
When the room
temperature drops
Tr - Ts ≥
-1.5°C
-2.5°C > Tr - Ts
Indoor heat exchanger
temperature drops
S-LOW
Indoor heat exchanger
temperature drops
- (04-57) -
-1.5°C
> Tr - Ts ≥
-2.5°C
34°C
31°C
29°C
24°C
34°C
31°C
29°C
24°C
3. Fan control

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents