Fujitsu AUXG07KVLA Manual page 216

2-unit multi-split type
Hide thumbs Also See for AUXG07KVLA:
Table of Contents

Advertisement

Check point 3. Check the solenoid coil and 4-way valve
Solenoid coil
Remove P60 from PCB and check the resistance value of coil. Resistance value is about 2.78
kΩ.
→ If it is open or abnormal resistance value, replace solenoid coil.
4-way valve
Check each piping temperature, and the location of the valve by the temperature difference.
If the value location is not proper, replace 4-way valve.
Check point 4. Check the voltage of 4-way valve
Check the voltage P60 of Main PCB.
→ Check if AC 198 V (AC 220 V -10%) to AC 264 V (AC 240 V +10%) appears at P60 of Main PCB.
Heating operation
→ If it is not voltage, Replace Main PCB.
Cooling operation
→ If it is voltage, Replace Main PCB.
Check point 5. Replace the main PCB
If Check Point 1 to 4 do not improve the symptom, replace the main PCB.
2-38. E: 99. 4-way valve error (Outdoor unit)
End
- (03-52) -