Fujitsu AUXG07KVLA Manual page 196

2-unit multi-split type
Hide thumbs Also See for AUXG07KVLA:
Table of Contents

Advertisement

2-19. E: 53. Drain pump error (Indoor unit)
Indicator
Indoor unit
Indoor unit main PCB
Detective actuator
Float switch
Forecast of cause
Check point 1. Check float switch
Check operation of float switch. (any blocking by dust, etc.)
Remove float switch and check ON/OFF switching operation by using a meter.
-> If float switch is abnormal, replace it.
Check point 2. Check connector and wire
Check loose contact of CN9 and shorted wire (pinched wire).
-> Replace float switch if the wire is abnormal
Check point 3. Check drain hose
Check drain hose.
-> If there is hose clogging. Please clear the clog.
Check point 4. Replace the main PCB
If check point 1 to 3 do not improve the symptom, replace the main PCB and execute the check
operation again.
Attention
Wall mount type does not have a float switch. In this case, replace main PCB and set up the origi-
nal address.
2-19. E: 53. Drain pump error (Indoor unit)
Operation indicator
Timer indicator
Economy indicator
Error code
When Float switch is ON for more than 3 minutes.
End
- (03-32) -
5 time flash
3 time flash
Continuous flash
E: 53
Float switch failure
Shorted connector/wire failure
Main PCB failure
Drain pump failure
Hose clogging
2. Troubleshooting with error code