Dry Operation - Fujitsu AUXG07KVLA Manual

2-unit multi-split type
Hide thumbs Also See for AUXG07KVLA:
Table of Contents

Advertisement

1-3. Dry operation

The rotation number of the compressor shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit has detected
as shown in the table below.
Zone is defined by set temperature and room temperature.
¢ Compact cassette type
• Rotation number range of compressor
– Model: AOHG14KBTA2
Model name
AUXG07KVLA
AUXG09KVLA
AUXG12KVLA
AUXG14KVLA
– Model: AOHG18KBTA2
Model name
AUXG07KVLA
AUXG09KVLA
AUXG12KVLA
AUXG14KVLA
• Compressor control based on room temperature
1-3. Dry operation
Outdoor temperature zone
Outdoor temperature zone
Room temperature drops
X zone
Ts+0.5°C
J zone
Ts
-1.5°C
Y zone
- (04-15) -
Operating rotation number
X zone
J zone
Y zone
X zone
J zone
Y zone
Operating rotation number
X zone
J zone
Y zone
X zone
J zone
Y zone
Room temperature rises
Ts+1.5°C
Ts-0.5°C
Ts: Set temperature
Unit: rps
50
50
0
44
44
0
50
50
0
42
42
0
1. Rotation number control of compressor