Fujitsu AUXG07KVLA Manual page 197

2-unit multi-split type
Hide thumbs Also See for AUXG07KVLA:
Table of Contents

Advertisement

2-20. E: 57. Damper (Open/Close) detection limit switch error
Indicator
Indoor unit
Indoor unit main PCB
Limit switch
Detective actuator
Damper
Forecast of cause
Check point 1. Check limit switch
Check operation of limit switch. (any blocking by dust, etc.)
Remove limit switch and check ON/OFF switching operation by using a meter.
-> If limit switch is detective, replace it.
Check point 2. Check connector (CN18)/wire
Check loose contact of CN18/shorted wire (pinched wire).
-> Replace limit switch if the wire is abnormal
Check point 3. Check Damper
Check the obstruction of damper movement.
Check the damper movement.
-> Replace damper if the damper is abnormal
Check point 4. Replace the main PCB
If Check Point 1 and 3 do not improve the symptom, replace the main PCB.
2-20. E: 57. Damper (Open/Close) detection limit switch error
Operation indicator
Timer indicator
Economy indicator
Error code
When limit switch were not able to detect the close
though the damper close.(Upper air flow)
When limit switch were not able to detect the open
though the damper open.(Upper & Lower air flow)
End
- (03-33) -
5 time flash
7 time flash
Continuous flash
E: 57
Limit switch failure
Shorted connector/wire
Damper faulure
Controller PCB failure
2. Troubleshooting with error code