2-41. E: A8. Refrigerant leakage sensor error (Indoor unit)

Indicator
Indoor unit
Detective actuator
Forecast of cause
Check point 1. Refrigerant leakage detection conditions
When the refrigerant leakage sensor detects refrigerant.
System stop -> Cooling/heating cannot be operated.
Stir operation by fan -> Safety is important, and fan operation cannot be stopped.
-> Check for refrigerant leaks and take corrective action.
Check point 2. Error release condition
Power on again.
If the power is not turned on again, the error will not be cleared even if the gas concentration
drops.
If the refrigerant leakage is detected again after the power is turned on again, an error will occur
again.
Replace the refrigerant leakage sensor as it will not recover if exposed to a high concentration
of gas or if exposed multiple times even if the concentration is not high.
2-41. E: A8. Refrigerant leakage sensor error (Indoor unit)
Operation indicator
Timer indicator
Economy indicator
Error code
End
- (03-57) -
10 time flash
8 time flash
Continuous flash
E: A8
Refrigerant leakage sensor
Refrigerant leakage
2. Troubleshooting with error code