3. DRY OPERATION

The compressor frequency shall change according to the temperature, set temperature,
and room temperature variation which the room temperature sensor of the indoor unit body has
detected as shown in the Table 4.
( Table 4 : Compressor frequency in Dry mode)
AO*G07/09/12KMTA, KMCC
X zone
J zone
Y zone
( Fig.2 : Compressor control based on room temperature )
Room
temperature
X zone
Ts+0.5°C
J zone
Ts -1.5°C
Y zone
Operating frequency
AO*G14KMTA, KMCC
24rps
18rps
0rps
Room
temperature
Ts+1.5°C
Ts -0.5°C
01-03