Error
D1RW COMM
TRNS Comm X
Side Marker
SDLT comm 1
Communication
No Photocell
Day to Night transition
Night to Day transition
Side Markers out
25% White
865 W25PCT 1
25% Red or Red+IR
864 R25PCT 1
D1_RS232
TRNS RS232 1
Relay Board
RLY Comm 1
Communication
LCD Alarm
Description
display
Comm Alarm
Side light board
communication
issue
Photocell not
PCE LOST
detected
There was an
issue with the
Day to Nite
transition from
Day to Night
There was an
issue with the
transition from
Nite to Day
Night Mode to
Day Mode
All Side Lights
ALL 810
are out
25% of the
white LED's are
out
>25% of LEDs
are out or Red
(+IR) failure
Translator
board
connection to
the microboard
in missing
Relay board
issue
Check TX,RX
and Tx_En if
flashing
Document No: 9100-127-1958-99 Rev E
How to generate it
Check: J1 (RS485) on the
translator board
Check: Check other side
in splitter board
Check: J2 (RS485) on the
monitor board
Check: J4 on monitor
board
Check: the red and black
for 48vdc
Check: wiring in photocell
to match J4
The system is in Day mode
for more than 18
hours
The system is in night
mode for more than 18
hours
Check: J1 of the monitor
board
Check: in night mode that
there is 48Vdc from J1 to
J6
Check White driver 1
Check: White driver 2
Check: Surge board wiring
to white and white/black
Check: J2 off of Red driver
Check: cables on red
driver
Check: Surge board wiring
to red and red/black
Check: both sides of the
RS232 Cable (J4) on the
Translator board
Check: J1 (RS485) on the
Relay board
Check: That the yellow and
black wires are connected
1501 Route 34 South, Farmingdale, NJ 07727 Tel: (732)
919-3119 Fax: (732) 751-5778 www.dialight.com
Corresponding Dry
Contact
Alarm 6
Alarm 1
Alarm 1
Alarm 4
Alarm 5
* event if PEC trans is
configured to NO
Alarm 5
* event if PEC trans is
configured to NO
Alarm 7
Alarm 3
Alarm 3
Alarm 6
All dry contacts will be
tripped
S7 on LCD lit
Alarm logged