Installation Tips and requirements:
For the Mains cable, it is recommended that the electrician or installer calculate the wire
requirements based on the amount of Flash heads being installed. It is recommended
that no install utilizes less than 16AWG wire with at least a 90
electrical parameters.
For RS485 cabling; 3 cores of 18AWG, drain wire plus a shield and braid for adequate
grounding and signals are required. RS485 is only required for E1+1 and larger
structures where multiple Strobes are required.
Cable between the Flash head and the controller must be a minimum of 14AWG and 4
conductors with foil and braid. Maximum distance between the controller and the Flash
head is 630feet.
NOTE: Failure to do any of the above could void all factory warranties. If in doubt please
contact your sales agent or representative.
During installing on the tower proper grounding techniques should be utilized.
The system has built in Lightning and RF immunity at each section, but for it to be
effective proper ground connection techniques must be used. For more details or
contact your local sales rep.
System Descriptions that are covered in the manual:
D1RW-C13-009-CTR = consists of:
D1RW-FH009 (Flash Head)
D1RW-CTR009 (Controller/Supply)
D1RW-C13-409-CTR = consists of:
D1RW-FH409 (Flash Head)
D1RW-CTR409 (Controller/Supply)
D1RW-C14-009-CTR = consists of:
D1RW-FH009 (Flash Head)
D1RW-CTR049 (Controller/Supply)
D1RW-C14-409-CTR = consists of:
D1RW-FH409 (Flash Head)
D1RW-CTR449 (Controller/Supply)
D1RW-C17-009-CTR = consists of:
D1RW-FH009 (Flash Head)
D1RW-CTR079 (Controller/Supply)
D1RW-C17-409-CTR = consists of:
D1RW-FH409 (Flash Head)
D1RW-CTR479 (Controller/Supply)
D1CW-C13-409-CTR = consists of:
D1CW-FH409 (Flash Head)
D1CW-CTR409 (Controller/Supply)
D1CW-C14-409-CTR = consists of:
D1CW-FH409 (Flash Head)
D1CW-CTR449 (Controller/Supply)
Document No: 9100-127-1958-99 Rev F
º
C temperature rating. See
Gen5 dual red/white with AC input , 48volt
sidelights and 8 conductor flash head cable
required
Gen5 dual red/white with AC input , 48volt
sidelights and 4 conductor flash head cable
required
Gen5 dual red/white with 48VDC input , 48volt
sidelights and 8 conductor flash head cable
required
Gen5 dual red/white with 48VDC input , 48volt
sidelights and 4 conductor flash head cable
required
Gen5 dual red/white with AC input , AC sidelights
and 8 conductor flash head cable required
Gen5 dual red/white with AC input , AC sidelights
and 4 conductor flash head cable required
Gen5 dual red/white + Infrared (IR) with AC input ,
48volt sidelights and 4 conductor flash head cable
required
Gen5 dual red/white + Infrared (IR) with 48VDC
input , 48volt sidelights and 8 conductor flash head
cable required