HYDAC ELECTRONIC ETS 3000 Operating Instructions Manual

HYDAC ELECTRONIC ETS 3000 Operating Instructions Manual

Electronic temperature switch with io-link interface
Hide thumbs Also See for ETS 3000:
Table of Contents

Advertisement

Available languages

Available languages

Quick Links

Bedienungsanleitung
(Originalanleitung)
Operating Instructions
(Translation of original
instructions)
Elektronischer
Temperaturschalter
Electronic Temperature Switch
ETS 3000
Mit IO-Link Schnittstelle
With IO-Link Interface

Advertisement

Chapters

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ETS 3000 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for HYDAC ELECTRONIC ETS 3000

  • Page 1 Elektronischer Temperaturschalter Electronic Temperature Switch ETS 3000 Mit IO-Link Schnittstelle With IO-Link Interface Bedienungsanleitung (Originalanleitung) Operating Instructions (Translation of original instructions)
  • Page 2: Table Of Contents

    Bestimmungsgemäßer Gebrauch / vorhersehbarer Fehlgebrauch Verpflichtung des Betreibers vor der Inbetriebnahme Personalauswahl und Qualifikation; Grundsätzliche Pflichten Organisatorische Maßnahmen Transport, Verpackung, Lagerung Transport Verpackung Lagerung Entsorgung Funktionen des ETS 3000 Wartung und Instandhaltung Montage Allgemeine Montagehinweise Zusätzliche Montagehinweise Bedienelemente des ETS 3000 Betriebsarten 11.1 SIO-Mode 11.2...
  • Page 3 ETS 3000 IO-Link Ausgangsverhalten 14.1 Schaltausgänge 14.1.1 Two-Point-Mode - Einstellung auf Schaltpunkt (SP) 14.1.2 Window-Mode - Einstellung auf Fensterfunktion (Fno / Fnc) 14.2 Einstellbereiche für die Schaltausgänge 14.3 Analogausgang Grundeinstellungen 15.1 Hauptmenü 15.2 Erweiterte Funktionen 15.3 Ändern der Grundeinstellungen Rücksetzen der Spitzenwerte Programmierfreigabe 17.1...
  • Page 4: Vorwort

    ETS 3000 IO-Link Vorwort Für Sie, den Benutzer unseres Produktes, haben wir in dieser Dokumentation die wichtigsten Hinweise zum Bedienen und Warten zusammengestellt. Sie dient Ihnen dazu, das Produkt kennen zu lernen und seine bestimmungsgemäßen Einsatzmöglichkeiten optimal zu nutzen. Diese Dokumentation muss ständig am Einsatzort verfügbar sein.
  • Page 5: Sicherheitshinweis

    ETS 3000 IO-Link Sicherheitshinweis Überprüfen Sie vor der Inbetriebnahme den Zustand des Gerätes sowie des mitgelieferten Zubehörs. Lesen Sie vor der Inbetriebnahme des Gerätes die Bedienanleitung und stellen Sie sicher, dass das Gerät für Ihre Anwendung geeignet ist. Falsche Handhabung bzw. die Nichteinhaltung von Gebrauchshinweisen oder technischen Angaben kann zu Sach- und / oder Personenschäden führen.
  • Page 6: Bestimmungsgemäßer Gebrauch / Vorhersehbarer Fehlgebrauch

    ETS 3000 IO-Link Das Symbol bezeichnet wichtige Informationen bzw. Merkmale und Anwendungstipps des verwendeten Produkts. Das Symbol bedeutet, dass entsprechende ESD-Schutzmaßnahmen nach DIN EN 100 015-1 zu beachten sind. (Herbeiführen eines Potentialausgleichs zwischen Körper und Geräte- masse sowie Gehäusemasse über einen hochohmigen Widerstand (ca.
  • Page 7: Organisatorische Maßnahmen

    Falls das Mess-Systems nach Ablauf der Lebensdauer entsorgt werden soll, sind die jeweils geltenden landesspezifischen Vorschriften zu beachten Funktionen des ETS 3000 Der ETS 3000 ist mit integriertem und mit externem Temperatursensor erhältlich. Je nach Ausführung bietet das Gerät folgende Funktionen:  Unterstützt IO-Link-Spezifikation V1.1 und V1.0 ...
  • Page 8: Wartung Und Instandhaltung

    Sie sich bitte an die HYDAC Systems & Services GmbH. Montage 9.1 Allgemeine Montagehinweise Der ETS 3000 mit integriertem Sensor kann über das Außengewinde (G1/2 A ISO 1179-2) direkt an einem Hydraulikblock montiert werden. Der Temperatursensor ist in dem vor dem Gewinde...
  • Page 9: Bedienelemente Des Ets 3000

    Bei Anschluss an Class B Ports nur 3-adrige Leitung mit PIN 1, 3 und 4 Belegung verwenden Bei Konfiguration von Pin 2 als zusätzlichem Analogausgang darf dieser grundsätzlich nicht mit dem Master verbunden werden. Bedienelemente des ETS 3000 Anzeige der Anzeige der HYDAC...
  • Page 10: Betriebsarten

    Im SDCI-Mode findet eine zyklische Übertragung der Prozessdaten zu dem angeschlossenen IO-Link-Master über den Kommunikations-Pin 4 statt. Der ETS 3000 liefert eine Prozessdatenbreite von 2 Byte. Für den eigentlichen Messwert („PDV“ = „Process Data Value“) werden 14 Bit verwendet. Es wird eine Dezimalstelle verwendet.
  • Page 11: Parametrierung

    Das Zip-file enthält zusätzlich eine pdf-Datei mit einer IODD-Beschreibung. 12.3 Parametrierung im SIO Mode Wird IO-Link nicht genutzt, so arbeitet der ETS 3000 IO-Link als Temperaturschalter mit 2 Schaltausgängen oder 1 Schaltausgang und 1 Analogausgang. Er kann mittels der integrierten Bedienknöpfe (Menüführung siehe Kapitel 15 Grundeinstellungen), mit dem HYDAC Programmiergerät HPG P1-000 oder dem HYDAC...
  • Page 12: Parametrierung Mit Hydac Programmiergerät Hpg P1-000

    ETS 3000 IO-Link 12.4 Parametrierung mit HYDAC Programmiergerät HPG P1-000 (Anschluss mit Standardkabel) HPG P1 Device Q1 / C 12.5 Parametrierung mit HYDAC Programmieradapter ZBE P1-000 (Anschluss mit Standardkabel) Q2 / QA ZBE P1 Device Q1 / C Darstellung der Digitalanzeige...
  • Page 13 ETS 3000 IO-Link Bezeichnung Darstellung Darstellung ASCII 7-Segment- Anzeige Rückschaltverzögerungszeit, DR 1 Ausgang 1 Rückschaltverzögerungszeit, Ausgang 2 OV 1 Ausgang 1 Ausgang 2 Stromausgang Spannungsausgang Schließer bei Fensterfunktion Öffner bei Fensterfunktion VN I Einheitenumschaltung Einheit °C °C Einheit °F °F...
  • Page 14: Ausgangsverhalten

    „Reset Min-/Max-Wert“ (RS.HL) bzw. „Rücksetzen“ (rES) erfolgt. Ausgangsverhalten 14.1 Schaltausgänge Der ETS 3000 IO-Link verfügt über 2 Schaltausgänge, deren Schaltverhalten (Window- Mode oder Two-Point-Mode) parametriert werden können. Ergänzend zu der IO-Link Smart Sensor Profile Specification kann bei HYDAC IO-Link Sensoren eine Schalt- und Rückschaltverzögerung parametriert werden.
  • Page 15: Window-Mode - Einstellung Auf Fensterfunktion (Fno / Fnc)

    ETS 3000 IO-Link 14.1.2 Window-Mode - Einstellung auf Fensterfunktion (Fno / Fnc) Die Fensterfunktion ermöglicht es, einen Bereich zu überwachen. Zu jedem Schalt- ausgang können jeweils ein oberer und ein unterer Schaltwert eingegeben werden, die den Bereich bestimmen. Der jeweilige Ausgang schaltet, wenn die Temperatur in diesen Bereich eintritt. Bei Verlassen des Bereiches, d.h.
  • Page 16: Einstellbereiche Für Die Schaltausgänge

    ETS 3000 IO-Link 14.2 Einstellbereiche für die Schaltausgänge Messbereich Untere Obere Mindestabstand Schrittweite* Grenze von Grenze von zw. RP und SP RP / FL SP / FH bzw. FL und FH Integrierter Sensor -25 .. +100 °C -23,8 °C 100,0 °C 1,2 °C...
  • Page 17: Grundeinstellungen

    ETS 3000 IO-Link Grundeinstellungen Zur Anpassung an die jeweilige Applikation kann das Verhalten des ETS 3000 über mehrere Grundeinstellungen verändert werden. Diese sind einem Menü zusammengefasst. 15.1 Hauptmenü Der Bereich wird nicht angezeigt, wenn in „Erweiterte Funktionen“ unter „ou2“ „i“ oder „u“...
  • Page 18: Erweiterte Funktionen

    ETS 3000 IO-Link 15.2 Erweiterte Funktionen Der Bereich wird nicht angezeigt, wenn in „Erweiterte Funktionen“ unter „ou2“ „i“ oder „u“ eingestellt ist. Stand: 13.07.2022 HYDAC ELECTRONIC GMBH Mat. Nr.: 669904 D...
  • Page 19: Ändern Der Grundeinstellungen

    ETS 3000 IO-Link 15.3 Ändern der Grundeinstellungen HINWEIS: Erfolgt ca. 60 Sekunden lang keine Tastenbetätigung wird das Menü automatisch beendet, ohne dass eventuelle Änderungen wirksam werden. Rücksetzen der Spitzenwerte Die Spitzenwerte der Temperatur können zurückgesetzt werden.  In den Erweiterten Funktionen die Taste "" betätigen bis der Menüpunkt „rSHL“...
  • Page 20: Programmierfreigabe

    ETS 3000 IO-Link Programmierfreigabe 17.1 Allgemeines Das Gerät verfügt über eine Programmierfreigabe, die erteilt sein muss, um Einstellungen zu ändern. Die Programmierfreigabe kann während des Betriebes gesetzt bzw. aufgehoben werden. Sie bietet Schutz vor unbeabsichtigten Änderungen. 17.2 Ändern der Programmierfreigabe ...
  • Page 21: Anschlussbelegung

    ETS 3000 IO-Link Anschlussbelegung M12x1, 4-polig Q1/C Q2/QA Signal Bezeichnung Q2/QA Schaltausgang (SP2) / Analogausgang Q1/C Schaltausgang (SP1) / IO-Link Kommunikation Stand: 13.07.2022 HYDAC ELECTRONIC GMBH Mat. Nr.: 669904 D...
  • Page 22: Technische Daten

    ETS 3000 IO-Link Technische Daten 20.1 ETS 3200 mit integriertem Sensor Eingangskenngrößen Messbereich -25 .. 100 °C (-13 .. 212 °F) Fühlerlänge Fühlerdurchmesser Druckfestigkeit 8700 Mechanischer Anschluss G1/2 A ISO 1179-2 Anzugsdrehmoment, empfohlen 45 Nm [33 ft-lb ] Medienberührende Teile Anschlussstück: Edelstahl;...
  • Page 23: Ets 3800 Für Externen Sensor

    Verpolungsschutz der Versorgungsspannung, Überspannungs-, Übersteuerungsschutz, Lastkurzschlussfestigkeit sind vorhanden. FS (Full Scale) = bezogen auf den vollen Messbereich Der Mediumstemperaturbereich des angeschlossenen Temperatursensors kann den Anzeigebereich des ETS 3000 reduzieren. Umgebungsbedingungen gemäß 1.4.2 UL 61010-1; C22.2 No. 61010-1 bei montierter Kupplungsdose entsprechender Schutzart Stand: 13.07.2022 HYDAC ELECTRONIC GMBH Mat.
  • Page 24: Io-Link-Spezifische Daten

    ETS 3000 IO-Link 20.3 IO-Link-spezifische Daten Features Block Parameter Data Storage Profile Characteristic 0x0001 (Device Profile: Smart Sensor), 0x8000 (Function Class: Device Identification), 0x8001 (Function Class: Binary Data Channel), 0x8002 (Function Class: Process Data Variables) Supported Access Locks Parameter Data Storage...
  • Page 25: Typenschlüssel

    ETS 3000 IO-Link Typenschlüssel 21.1 ETS 3200 mit integriertem Sensor ETS 3 2 2 X - F31 - XXX - X00 Ausführung 2 = Mit integriertem Temperaturfühler Anschlussart, mechanisch 2 = G1/2 A ISO 1179-2 Anschlussart, elektrisch 6 = Gerätestecker M12x1, 4-pol.
  • Page 26: Ets 3800 Für Externen Sensor

    ETS 3000 IO-Link 21.2 ETS 3800 für externen Sensor ETS 3 8 6 X - F31 - 000 - X00 Ausführung 8 = Für externen Temperaturfühler Anschlussart, mechanisch 6 = Kabelbuchse M12x1, 4-pol. Anschlussart, elektrisch 6 = Gerätestecker M12x1, 4-pol.
  • Page 27: Zubehör

    ETS 3000 IO-Link Zubehör 22.1 Elektrischer Anschluss ZBE 06 (4-pol.) Kupplungsdose M12x1, abgewinkelt Kabeldurchmesser: 3,3 .. 6,6 mm (0.13 .. 0.26 inch) Material-Nr.: 6006788 ZBE 06-02 (4-pol.) Kupplungsdose M12x1, abgewinkelt mit 2 m (78,7 inch) Leitung, Material-Nr.: 6006790 ZBE 06-05 (4-pol.),...
  • Page 28: Mechanischer Anschluss

    ETS 3000 IO-Link 22.2 Mechanischer Anschluss ZBM 3000 Schelle zur Wandbefestigung, anschraubbar (Werkstoff Unterteil: TPE Santoprene 10187; Oberteil: Bandstahl DIN 95381-1.4571) Material-Nr.: 3184630 ZBM 3100 Schelle zur Wandbefestigung, anschweißbar (Werkstoff Schweißlasche: QSTE340TM, galvanischer Überzug EN 12329 FE/ZN8/B; Unterteil: TPE Santoprene 10187; Oberteil: Bandstahl DIN 95381-1.4571) Material-Nr.: 3184632...
  • Page 29 ETS 3000 IO-Link ZBM 3200 Spritzwasserschutz (Werkstoff: Elastollan S60 A15 SPF 000) Material-Nr.: 3201919 Stand: 13.07.2022 HYDAC ELECTRONIC GMBH Mat. Nr.: 669904 D...
  • Page 30 Bestell-Nr.: 906170 Technische Daten Druckfestigkeit 10 bar (145 psi) Werkstoff in Kontakt mit Medium CuZn39Pb3 (Messing), vernickelt Tankeinbauhülse für ETS 3000 mit integriertem Sensor, Fühlerlänge 100 mm Bestell-Nr.: 909640 Technische Daten Druckfestigkeit 10 bar (145 psi) Werkstoff in Kontakt mit Medium CuZn39Pb3 (Messing), vernickelt Stand: 13.07.2022...
  • Page 31: Externer Pt100 Sensor

    ETS 3000 IO-Link 22.3 Externer PT100 Sensor 22.3.1 Abmessungen und technische Daten Typenbezeichnung: TFP 104-000 Typenbezeichnung: TFP 106-000 Bestell-Nr.: 904696 Bestell-Nr.: 921330 Technische Daten Messelement PT 100 Messbereich -40 .. +125 °C ( -40 .. +257 °F) Fühlerlänge 95,5 mm Fühlerdurchmesser...
  • Page 32: Geräteabmessungen

    ETS 3000 IO-Link Geräteabmessungen 23.1 ETS 3200 mit integriertem Sensor Fühlerlänge (Maß Z) 23.2 ETS 3800 für externen Sensor Stand: 13.07.2022 HYDAC ELECTRONIC GMBH Mat. Nr.: 669904 D...
  • Page 33: Abkürzungsverzeichnis

    ETS 3000 IO-Link Abkürzungsverzeichnis Wert-Fenster oberer Wert Wert-Fenster unterer Wert Fensterfunktion Öffner Fensterfunktion Schließer Full Scale IODD IO Device Description ISDU Indexed Service Data Unit Ausgangsfunktion Rückschaltpunkt SDCI Single-drop digital communication interface Standard IO-Modus Schaltpunkt Schaltsignalkanal Stand: 13.07.2022 HYDAC ELECTRONIC GMBH...
  • Page 34: Kontakt

    ETS 3000 IO-Link Kontakt HYDAC ELECTRONIC GMBH Hauptstr. 27 D-66128 Saarbrücken Germany Web: www.hydac.com E-Mail: electronic@hydac.com Tel.: +49 (0)6897 509-01 Fax.: +49 (0)6897 509-1726 HYDAC Service Für Fragen zu Reparaturen steht Ihnen der HYDAC Service zur Verfügung. HYDAC SYSTEMS & SERVICES GMBH Hauptstr.
  • Page 35 Electronic Temperature Switch ETS 3000 with IO-Link Interface Operating Instructions (Translation of original instructions)
  • Page 36 Transportation, Packaging, Storage Transport Packaging Storage Disposal Functions of the ETS 3000 Maintenance and servicing Assembly General installation notes Additional installation instructions Operating Keys of the ETS 3000 Operation modes 11.1 SIO mode 11.2 SDCI-Mode Parameterisation 12.1 General 12.2 Parameterisation in SDCI mode 12.3...
  • Page 37 ETS 3000 IO-Link Output Signals 14.1 Switching outputs 14.1.1 Two-point mode - Switch point setting (SP) 14.1.2 Window mode - Window function setting (Fno / Fnc) 14.2 Setting ranges for the switching outputs 14.3 Analogue output Basic Settings 15.1 Main menu 15.2...
  • Page 38: Preface

    ETS 3000 IO-Link Preface The instructions provide you, as user of our product, with key information on the operation and maintenance of the equipment. It will help you to familiarise yourself with the product and assist you in obtaining maximum benefit in the applications for which it is designed.
  • Page 39: Safety Information

    ETS 3000 IO-Link Safety Information Before commissioning, check the device and all accessories supplied. Before commissioning, please read the operating instructions. Ensure that the instrument is suitable for your application. If the instrument is not handled correctly, or if the operating instructions and specifications are not adhered to, damage to property and/or personal injury can result.
  • Page 40: Intended Use / Foreseeable Misuse

    ETS 3000 IO-Link The symbol indicates important information or features and application suggestions for the product used. The symbol means that appropriate ESD-protective measures must be considered according to DIN EN 100 015-1. (Cause of a potential equalisation between body and device-mass as well as the housing-mass about a high-impedance resistance (approx.
  • Page 41: Organisational Measures

    If the measuring system has to be disposed after expiry of its life cycle, the corresponding national regulations are applicable. Functions of the ETS 3000 The ETS 3000 is available with an integral sensor probe and with an external temperature sensor probe. Depending on the model, the instrument has the following functions: ...
  • Page 42: Maintenance And Servicing

    Assembly 9.1 General installation notes The ETS 3000 with integrated sensor probe can be screwed directly into a hydraulic block via the male thread (G1/2 A ISO 1179-2 , (DIN 3852)). The temperature sensor is built into the stem before the thread. In order to perform correct measurements, ensure the probe is fully immersed in the fluid.
  • Page 43: Operating Keys Of The Ets 3000

    When connecting the Class B Ports, 3 core leads with PIN 1, 3 and 4 may be used only. Configuring pin 2 as an additional analogue output, this may no more be connected with the master under any circumstances. Operating Keys of the ETS 3000 Anzeige der Display of HYDAC...
  • Page 44: Operation Modes

    4 to the connected IO-Link master. The ETS 3000 provides a process data width of 2 bytes. 14 bits are used for the actual measured value ("PDV" = "Process data value"). The standard used is one decimal place.
  • Page 45: Parameterisation

    The Zip file has an additional PDF file with an IODD description. 12.3 Parameterisation in SIO Mode If IO-Link is not used, the ETS 3000 IO-Link functions as a temperature switch with two switching outputs or with 1 switching output and 1 analogue output.
  • Page 46: Parameterisation With Hydac Programming Device Hpg P1-000

    ETS 3000 IO-Link 12.4 Parameterisation with HYDAC programming device HPG P1-000 (Connection via standard cable) HPG P1 Device Q1 / C 12.5 Parameterisation by means of HYDAC programming adapter ZBE P1-000 (Connection via standard cable) Q2 / QA ZBE P1...
  • Page 47 ETS 3000 IO-Link Designation Representation on ASCII 7-segment display representation Switch-back delay time, Output 2 OV 1 Output 1 Output 2 Current output Voltage output N/O when window function is active N/C when window function is active VN I Unit conversion Unit °C...
  • Page 48: Output Signals

    "reset min/max value" or (rES) for "reset", has been carried out. Output Signals 14.1 Switching outputs The ETS 3000 IO-Link has 2 switching outputs whose switching behaviour (window mode or two-point mode) is parameterisable. In addition to the IO-Link Smart Sensor Profile Specification, a switch and switch-back delay can be set in HYDAC IO-Link sensors.
  • Page 49: Window Mode - Window Function Setting (Fno / Fnc)

    ETS 3000 IO-Link 14.1.2 Window mode - Window function setting (Fno / Fnc) The window function enables a range to be monitored. An upper and a lower switch point which defines the range can be assigned to each switching output.
  • Page 50: Setting Ranges For The Switching Outputs

    ETS 3000 IO-Link 14.2 Setting ranges for the switching outputs Measurement Lower limit Upper limit Minimum Increment* range of RP / FL of SP / FH difference betw. RP and SP or FL and FH Integrated sensor -25 .. +100 °C -23.8 °C...
  • Page 51: Basic Settings

    ETS 3000 IO-Link Basic Settings The function of the ETS 3000 can be adapted to suit the particular application by altering several basic settings. These settings are combined in a menu. 15.1 Main menu The range is not displayed if "i"...
  • Page 52: Add-On Functions

    ETS 3000 IO-Link 15.2 Add-on functions The range is not displayed if "i" or "u" is pre-set under "ou2" in the "extended functions". Status: 2022-07-13 HYDAC ELECTRONIC GMBH Part No.: 669904 E...
  • Page 53: Changing The Basic Settings

    ETS 3000 IO-Link 15.3 Changing the Basic Settings Note: If there has been no activity in this menu for approx. 60 seconds, the menu will automatically close and any changes you have made will not be applied. Resetting the peak values The peak values of the temperature level can be set back.
  • Page 54: Program Enable

    ETS 3000 IO-Link Program enable 17.1 General The instrument has a program enable which must be set to change the settings. The program enable can be set or cancelled during operation. It provides protection against unintentional alterations of settings. 17.2 Changing the Programming Enable ...
  • Page 55: Pin Connection

    ETS 3000 IO-Link PIN connection M12x1, 4 pole Q1/C Q2/QA Signal Designation Q2/QA Switching output (SP2) / Analogue output Q1/C Switching output (SP1) / IO-Link Communication Status: 2022-07-13 HYDAC ELECTRONIC GMBH Part No.: 669904 E...
  • Page 56: Technical Data

    ETS 3000 IO-Link Technical Data 20.1 ETS 3200 with integrated sensor probe Input data Measurement range -25 .. 100 °C [-13 .. 212 °F) Probe length Probe diameter Pressure resistance 8700 Mechanical connection G1/2 A ISO 1179-2 Tightening torque, recommended...
  • Page 57: Ets 3800 For External Sensor Probe

    FS (Full Scale) = relative to complete measuring range Depending on the temperature range of the connected temperature sensor, the indication range of the ETS 3000 may be reduced. Environmental conditions according to 1.4.2 UL 61010-1; C22.2 no. 61010-1 with mounted mating connector in corresponding protection type...
  • Page 58: Io-Link Specific Data

    ETS 3000 IO-Link 20.3 IO-Link specific data Features Block Parameter Data Storage Profile Characteristic 0x0001 (Device Profile: Smart Sensor), 0x8000 (Function Class: Device Identification), 0x8001 (Function Class: Binary Data Channel), 0x8002 (Function Class: Process Data Variables) Supported Access Locks Parameter...
  • Page 59: Model Code

    ETS 3000 IO-Link Model Code 21.1 ETS 3200 with integrated sensor probe ETS 3 2 2 X - F31 - XXX - X00 Design 2 = With integrated temperature probe Mechanical connection 2 = G1/2 A ISO 1179-2 Electrical connection...
  • Page 60: Ets 3800 For External Sensor Probe

    ETS 3000 IO-Link 21.2 ETS 3800 for external sensor probe ETS 3 8 6 X - F31 - 000 - X00 Design 8 = For external temperature probe Mechanical connection 6 = Socket M12x1, 4 pole Electrical connection 6 = Plug M12x1, 4 pole...
  • Page 61 ETS 3000 IO-Link Accessories 22.1 Electrical connection ZBE 06 (4 pole) Mating connector M12x1, right-angled Cable diameter: 3.3 .. 6.6 mm (0.13 .. 0.26 inch) Part No.: 6006788 ZBE 06-02 (4 pole) Mating connector M12x1, right-angle with 2 m (78.7 inch) cable, Part No.: 6006790...
  • Page 62 ETS 3000 IO-Link 22.2 Mechanical connection ZBM 3000 Clamp for wall-mounting, screw-type fitting (Material of lower section: TPE Santoprene 10187; Material of top section: Steel strip DIN 95381-1.4571) Part no.: 3184630 ZBM 3100 Clamp for wall-mounting,weld-type fitting (Material of welding bridge: QSTE340TM, zinc coating EN 12329 FE/ZN8/B;...
  • Page 63 ETS 3000 IO-Link ZBM 3200 Splash guard (Material: Elastollan S60 A15 SPF 000) Part no.: 3201919 Status: 2022-07-13 HYDAC ELECTRONIC GMBH Part No.: 669904 E...
  • Page 64 Technical Data Pressure resistance 10 bar (145 psi) Material in contact with fluid CuZn39Pb3 (brass), nickel-plated Tank mounting sleeve for ETS 3000 with integrated sensor probe, probe length: 100 mm Order no.: 909640 Technical Data Pressure resistance 10 bar (145 psi)
  • Page 65: External Pt100 Sensor

    ETS 3000 IO-Link 22.3 External PT100 Sensor 22.3.1 Dimensions and technical data Type designation: TFP 104-000 Type designation: TFP 106-000 Order no.: 904696 Order no.: 921330 Technical Data Measuring element PT 100 Measurement range -40 .. +125 °C ( -40 .. +257 °F) Probe length 95.5 mm...
  • Page 66: Device Dimensions

    ETS 3000 IO-Link Device dimensions 23.1 ETS 3200 with integrated sensor probe Probe length (dim. Z) 23.2 ETS 3800 for external sensor probe Status: 2022-07-13 HYDAC ELECTRONIC GMBH Part No.: 669904 E...
  • Page 67: List Of Abbreviations

    ETS 3000 IO-Link List of abbreviations Value window upper value Value window lower value Window function, N/C Window function, N/O Full Scale IODD IO Device Description ISDU Indexed Service Data Unit Output function Switch-back point SDCI Single-drop digital communication interface...
  • Page 68: Contact

    ETS 3000 IO-Link Contact HYDAC ELECTRONIC GMBH Hauptstrasse 27 D-66128 Saarbruecken Germany Web: www.hydac.com Email: electronic@hydac.com Phone: +49 (0)6897 509-01 Fax.: +49 (0)6897 509-1726 HYDAC Service For enquiries about repairs or alterations, please contact HYDAC Service. HYDAC SYSTEMS & SERVICES GMBH...
  • Page 69: Anhang / Annex: Iodd Einstellparameter / Iodd Setting Parameters

    ETS 3000 IO-Link Anhang / Annex: IODD Einstellparameter / IODD Setting Parameters Die Einstellparameter des ETS 3000 am The setting parameters of the ETS 3000 Beispiel eines Gerätes mit 100 mm Fühler- using the example of a device with a länge finden Sie auf den nachfolgenden...
  • Page 70 ETS 3000 IO-Link Standard Variable "Standard Command" index=2 id=V_SystemCommand data type: 8-bit UInteger allowed values: 128 = Device Reset, 129 = Application Reset, 130 = Restore Factory Settings, 160 = Reset Primary Min/Max, 164 = Reset All Min/Max access rights: wo...
  • Page 71 ETS 3000 IO-Link Variable "BDC1 Behavior" index=61 id=V_Bdc1Behavior data type: 32-bit Record (subindex access not supported) access rights: rw modifies other variables excluded from data storage allowed default subindex data type mod. other var. name description offset values value 0 = Default, 1...
  • Page 72 ETS 3000 IO-Link octet bit offset 31 - 24 23 - 16 15 - 8 7 - 0 subindex element bit 7 - 0 7 - 0 15 - 8 7 - 0 Variable "Primary Value SP1" index=64 id=V_PrimaryValueSp1 data type: 112-bit Record (subindex access not supported)
  • Page 73 ETS 3000 IO-Link octet bit offset 111 - 104 103 - 96 95 - 88 87 - 80 79 - 72 71 - 64 63 - 56 55 - 48 subindex element bit 7 - 0 7 - 0 15 - 8...
  • Page 74 ETS 3000 IO-Link Variable "Display Mapping" index=75 id=V_DspMapping data type: 8-bit UInteger allowed values: 0 = Primary Value default value: 0 access rights: rw octet bit offset 7 - 0 element bit 7 - 0 Variable "Primary Value Display Unit" index=76 id=V_PrimaryValueDspUnit...
  • Page 75 ETS 3000 IO-Link Octet 1 bit offset subindex element bit Octet 2 bit offset subindex / / / / / / / / / / / / / / / / / / / / / / / / Variable "Primary Maximum Value" index=92 id=V_PrimaryMaxValue...
  • Page 76 ETS 3000 IO-Link ErrorTypes Additional Code Name Description code Device application error - Service has been refused by the device application and no 128 (0x80) 0 (0x00) no details detailed information of the incident is available 128 (0x80) 17 (0x11)